Installation
If six POPITs are assigned in programming to each of five master zones, and one POPIT has erroneous switch settings (see
Figure 16), Master Zone 5 appears to have only five POPITs installed, and Master Zone 7 (which has no POPITs assigned in
programming) appears to have one POPIT installed. Both “missing and extra POPIT conditions will be displayed on the
D1252A.
2.5 Z1POINTS 6
2.12 Z8POINTS 00
PROGRAMMED
2.6 Z2POINTS 6
2.7 Z3POINTS 6
2.8 Z4POINTS 6
2.9 Z5POINTS 6
2.10 Z6POINTS 00
2.11 Z7POINTS 00
MASTER ZONE 1: 6
MASTER ZONE 2: 6
MASTER ZONE 3: 6
MASTER ZONE 4: 6
MASTER ZONE 5: 5
MISSING
POPIT
MASTER ZONE 7: 1
EXTRA
POPIT
INSTALLED
Figure 16: POPIT Switch Setting Error
Figure 17 also displays a system containing one POPIT with erroneous switch settings. Both “missing” and “extra POPIT
conditions will be displayed on the D1252A after entering a [Command 44].
2.5 Z1POINTS 6
2.12 Z8POINTS 00
PROGRAMMED
2.6 Z2POINTS 6
2.7 Z3POINTS 6
2.8 Z4POINTS 6
2.9 Z5POINTS 6
2.10 Z6POINTS 00
2.11 Z7POINTS 00
MASTER ZONE 1: 6
MASTER ZONE 2: 6
MASTER ZONE 3: 6
MASTER ZONE 4: 5
MASTER ZONE 5: 7
MISSING
POPIT
EXTRA
POPIT
INSTALLED
Figure 17: POPIT Switch Setting Error