EasyManuals Logo

Bosch EV2000 Series User Manual

Bosch EV2000 Series
39 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #6 background imageLoading...
Page #6 background image
579604 | REV. C | June 2020
Bosch Automotive Service Solutions Inc.
EV2000 Series Wallbox Charger Installation and Operation Manual|
3
|
en
3.0 Before Installation
3.1 Safety Requirements
` Be sure to preview the standard operating proce-
dures (SOP) and ensure local building andelectrical
codes are reviewed before installing the DC Wallbox
charger.
` The DC Wallbox charger should be installed by a
qualied technician according to the instruction
manual and local safety regulations.
` Use appropriate protection when connecting to the
main power distribution cable.
` Disconnect switch for each ungrounded conductor of
AC input shall be provided by others in accordance
with the National Electric Code, ANSI/NFPA 70.
CAUTION TO REDUCE RISK OF FIRE,
FOR 1 PHASE 200VAC-277VAC INPUT,
IN ACCORDANCE WITH THE NATIONAL
ELECTRIC CODE, ANSI/NFPA 70, THE
UPSTREAM CIRCUIT BREAKER SHOULD BE
INSTALLED WITH A RATED CURRENT OF
175A.
CAUTION TO REDUCE RISK OF FIRE, FOR
3 PHASE 480VAC INPUT, IN ACCORDANCE
WITH THE NATIONAL ELECTRIC CODE,
ANSI/NFPA 70, THE UPSTREAM CIRCUIT
BREAKER SHOULD BE INSTALLED WITH A
RATED CURRENT OF 40A.
CAUTION TO REDUCE RISK OF FIRE, FOR
3 PHASE 208VAC INPUT, IN ACCORDANCE
WITH THE NATIONAL ELECTRIC CODE,
ANSI/NFPA 70, THE UPSTREAM CIRCUIT
BREAKER SHOULD BE INSTALLED WITH A
RATED CURRENT OF 100A.
3.2 Accessory Kit
3.3 Recommended Tools
The following tools are recommended for DC Wallbox
Charger installation:
` (1x) Voltmeter or digital multi-meter
` (1x) Water level
` (1x) Hammer
` (1x) Concrete drilling machine
` (1x) Wire cutters / strippers
` (1x) Torx® Tamper-Resistant T20 screwdriver
` (1x) No.8 Flathead screwdriver
` (1x) No.6 Flathead screwdriver
` (1x) No.2 Philips screw driver
` (1x) M50 conduit hub, conduit and wrench for main
power wires
` (1x) M25 conduit hub, conduit and wrench for
Ethernet
` (2x) Ring terminal RNB70-10 for L/N wire (#2/0
AWG, 90°C copper wire) in models with 240V and
277V single-phase input
` (3x) Ring terminal RNB38-6 for L1/L2/L3 wire (#2
AWG, 90°C copper wire) in models with 208V three-
phase input
` (4x) Ring terminal RNB14-6 for L1/L2/L3/N wire (#6
AWG, 90°C copper wire) in models with 480V three-
phase input
` (1x) Ring terminal RNB14-6 for PE/ground wire (#6
AWG, 90°C copper wire)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch EV2000 Series and is the answer not in the manual?

Bosch EV2000 Series Specifications

General IconGeneral
BrandBosch
ModelEV2000 Series
CategoryBattery Charger
LanguageEnglish

Related product manuals