579604 | REV. C | June 2020
Bosch Automotive Service Solutions Inc.
EV2000 Series Wallbox Charger Installation and Operation Manual|
3
|
en
3.0 Before Installation
3.1 Safety Requirements
` Be sure to preview the standard operating proce-
dures (SOP) and ensure local building andelectrical
codes are reviewed before installing the DC Wallbox
charger.
` The DC Wallbox charger should be installed by a
qualied technician according to the instruction
manual and local safety regulations.
` Use appropriate protection when connecting to the
main power distribution cable.
` Disconnect switch for each ungrounded conductor of
AC input shall be provided by others in accordance
with the National Electric Code, ANSI/NFPA 70.
CAUTION TO REDUCE RISK OF FIRE,
FOR 1 PHASE 200VAC-277VAC INPUT,
IN ACCORDANCE WITH THE NATIONAL
ELECTRIC CODE, ANSI/NFPA 70, THE
UPSTREAM CIRCUIT BREAKER SHOULD BE
INSTALLED WITH A RATED CURRENT OF
175A.
CAUTION TO REDUCE RISK OF FIRE, FOR
3 PHASE 480VAC INPUT, IN ACCORDANCE
WITH THE NATIONAL ELECTRIC CODE,
ANSI/NFPA 70, THE UPSTREAM CIRCUIT
BREAKER SHOULD BE INSTALLED WITH A
RATED CURRENT OF 40A.
CAUTION TO REDUCE RISK OF FIRE, FOR
3 PHASE 208VAC INPUT, IN ACCORDANCE
WITH THE NATIONAL ELECTRIC CODE,
ANSI/NFPA 70, THE UPSTREAM CIRCUIT
BREAKER SHOULD BE INSTALLED WITH A
RATED CURRENT OF 100A.
3.2 Accessory Kit
3.3 Recommended Tools
The following tools are recommended for DC Wallbox
Charger installation:
` (1x) Voltmeter or digital multi-meter
` (1x) Water level
` (1x) Hammer
` (1x) Concrete drilling machine
` (1x) Wire cutters / strippers
` (1x) Torx® Tamper-Resistant T20 screwdriver
` (1x) No.8 Flathead screwdriver
` (1x) No.6 Flathead screwdriver
` (1x) No.2 Philips screw driver
` (1x) M50 conduit hub, conduit and wrench for main
power wires
` (1x) M25 conduit hub, conduit and wrench for
Ethernet
` (2x) Ring terminal RNB70-10 for L/N wire (#2/0
AWG, 90°C copper wire) in models with 240V and
277V single-phase input
` (3x) Ring terminal RNB38-6 for L1/L2/L3 wire (#2
AWG, 90°C copper wire) in models with 208V three-
phase input
` (4x) Ring terminal RNB14-6 for L1/L2/L3/N wire (#6
AWG, 90°C copper wire) in models with 480V three-
phase input
` (1x) Ring terminal RNB14-6 for PE/ground wire (#6
AWG, 90°C copper wire)