Selectable installation locations in
the programming software (WinPara
and FSP‑5000‑RPS)
Detector Type Sensitivity
Thermom
ax (T
max
)
Optical
(O)
Chemical
(C)
EDP room O, T
max
, T
diff
, C High (A2) High High
Production location O, T
max
, T
diff
, C Low (B) Low* Medium
Garage O, T
max
, T
diff
, C High (A2) Low* Low
High storage warehouse without
vehicle traffic with combustion
engine
O, T
max
, T
diff
, C Low (B) High High
Conference hall/waiting room/
fairground
O, T
max
, T
diff
, C High (A2) Low* Medium
Kitchen/casino/restaurant during
active operation
O, T
max
, C Low (B) Low* Low
Warehouse with vehicle traffic O, T
max
, T
diff
, C Low (B) Low* Low
Rate of rise only (optical sensor off) T
max
, T
diff
High (A2) - -
Optical only (thermal sensor off)*** O - Low -
Fixed temperature heat only (optical
sensor off)
T
max
High (A2) - -
Optical/chemical (thermal sensor
off)***
O, C - Low High
Schools/kindergarten O, T
max
, T
diff
, C High (A2) Medium High
Theater/concert hall O, T
max
, T
diff
, C High (A2) Medium High
O = optical sensor (dual-optical in FAP-DOTC420 detectors)
T
max
= thermal maximum unit
T
diff
= thermal differential unit
C = chemical sensor
* If optical sensor sensitivity is low, the detector will only trigger if smoke as well as an
increase in CO concentration or temperature is detected.
*** For FAP-DOTC420: does not comply with EN54-7
For details on installation height, see FAH-T 420/FAH-T 420-KKW, page 14
FAP‑DOT420 / FAP-OT 420
Notice!
The default setting of the FAP-DOT 420 and FAP-OT 420 detector types in RPS and WinPara is
"Office (day mode)". For a description of this setting, see the below table.
4.2
12 en | Programming
Automatic Fire Detectors LSN
improved
12/2012 | 8.1 | F.01U.003.448 Operation Guide Bosch Sicherheitssysteme GmbH