Selectable installation locations in the
programming software (WinPara and
FSP‑5000‑RPS)
Detector Type Sensitivity
Thermomax
(T
max
)
Optical
(O)
Office (after hours) O, T
max
, T
diff
High (A2) High
Office (smoker)/waiting room/restaurant/
meeting room
O, T
max
, T
diff
High (A2) Low
Office (day mode)
= default setting
O, T
max
, T
diff
Low (B) Medium
EDP room O, T
max
, T
diff
High (A2) High
Production location O, T
max
, T
diff
Low (B) Low
Garage
FAP-OT 420
FAP-DOT420
T
max
, T
diff
T
max
, T
diff
High (A2)
High (A2)
-
Low
High storage warehouse without vehicle traffic
with combustion engine
O, T
max
, T
diff
Low (B) High
Conference hall/waiting room/fairground O, T
max
, T
diff
High (A2) Low
Kitchen/casino/restaurant during active
operation
T
max
Low (B) -
Warehouse with vehicle traffic O, T
max
, T
diff
Low (B) Low
Rate of rise only (optical sensor off) T
max
, T
diff
High (A2) -
Optical only (thermal sensor off) O - Low
Fixed temperature heat only (optical sensor
off)**
T
max
High (A2) -
Schools/kindergarten O, T
max
, T
diff
High (A2) Medium
Theatre/concert hall O, T
max
, T
diff
High (A2) Medium
O = optical sensor (dual-optical in FAP-DOT420 detectors)
T
max
= thermal maximum unit
T
diff
= thermal differential unit
For details on installation height, see FAH-T 420/FAH-T 420-KKW, page 14
FAP‑DO420 / FAP-O 420 / FAP-O 420-KKW
i
Notice!
The default setting of the FAP-DO 420 and FAP-O 420 detector types in RPS and WinPara is
"Medium". For a list of possible installation locations and corresponding sensitivity settings,
see the below table.