Water-To-Water Unit Controller | 27Greensource CDi Series TW Model
8733954853 (2020/04)Greensource CDi Series TW Model
Subject to change without prior notice
4. Disconnect the yellow wire labeled D and black
wire labeled C. (See Fig. 17)
Fig. 17 Disconnect D and C
5. Connect yellow wire labeled A to yellow wire
labeled D. (See Fig. 18)
Fig. 18 Connect A and D
6. Leave black wires labeled B and C
disconnected. (See Fig. 15)
Fig. 19 Leave B and C Disconnected
This completes the Freeze Stat Bypass Field
Rework. (See Fig. 20)
Fig. 20 Completed Wiring
Initial Configuration
After power up and the steps above are completed
the configuration default settings may be changed.
Holding down the up and down arrow buttons
simultaneously for 10 seconds will put the
controller into the configuration mode. This mode
will be exited if no other commands are given
within a 10 second period.