    Latoya BoothSep 7, 2025
    How to troubleshoot a Bosch Heat Pump with no compressor operation but running fan, possibly due to blocked return air?
    • D
      deckermichaelSep 7, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a condensate fault caused by blocked return air. Check the condensate pan for a high water level. Also, check the air filter and return air duct work for blockage, and ensure there is adequate space between the return air opening and any obstructions.
  • R
    Ricardo JenkinsAug 22, 2025
    Why is my Bosch LV070 Heat Pump not shifting into cooling?
    • M
      Michelle JamesAug 22, 2025
      If your Bosch Heat Pump isn't shifting into cooling mode, check that the reversing valve solenoid is receiving 24 VAC. If it is, check the resistance of the solenoid; an open circuit may indicate a burned out solenoid. Also, check that the reversing valve thermostat wire is connected to the 'O' terminal of the thermostat and check for a contact closure between 'O' and 'R'. Finally, check that the wires from the thermostat to the unit are securely connected and that the wires from the electrical box to the reversing valve are connected.
  • D
    Daniel SchmidtSep 4, 2025
    What to do if the compressor of my Bosch LV070 doesn't work but the fan runs and there is a freeze fault caused by low refrigerant?
    • A
      Amanda JenkinsSep 4, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a freeze fault in the air coil caused by low refrigerant. Check the refrigerant pressure with a gauge set.
  • M
    Mrs. Lauren LopezSep 3, 2025
    How to troubleshoot a Bosch Heat Pump with no compressor operation but running fan, possibly due to a bad thermostat connection?
    • K
      Kelsey HardinSep 3, 2025
      If the compressor of your Bosch Heat Pump is not working, but the fan is running, it might be due to a brown-out fault caused by a bad thermostat connection. Check that the thermostat wiring is of the proper gauge and length, is undamaged, and that all connections at the thermostat and heat pump are secure.
  • R
    Rachel RobertsSep 2, 2025
    What to do if my Bosch LV070 compressor isn't running but the fan is on and I suspect an overloaded control circuit?
    • R
      Ricardo DavisSep 2, 2025
      If the compressor of your Bosch Heat Pump is not working, but the fan is running, it might be due to a brown-out fault caused by an overloaded control circuit. Check the control voltage; if it's below 18V, inspect the accessories connected to the unit and ensure they don't exceed the VA draw.
  • A
    afrazierAug 31, 2025
    Why is my Bosch LV070 compressor not running but the fan is, possibly due to low airflow?
    • I
      Isaac PaulSep 1, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a low-pressure fault caused by no or low airflow. Check the fan motor to ensure it is operating correctly.
  • R
    Rita CallahanAug 30, 2025
    What to do if my Bosch LV070 Heat Pump compressor isn't running but the fan is, and I suspect airflow issues?
    • L
      Louis ChapmanAug 30, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a high-pressure fault caused by no or low airflow. Check the fan motor to ensure it is operating correctly.
  • I
    imasseyAug 29, 2025
    How to troubleshoot a Bosch LV070 Heat Pump with no compressor operation but running fan, possibly due to a fouled water coil?
    • R
      Roger SwansonAug 29, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a high-pressure fault caused by a fouled or scaled water coil. Check for proper flow rate and water temperature, especially looking for a low water side temperature rise during cooling.
  • J
    jessicaturnerAug 27, 2025
    Why is my Bosch Heat Pump compressor not running but the fan is, possibly due to high water temperature?
    • K
      Keith MartinezAug 28, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a high-pressure fault caused by high water temperature. Check the water temperature to ensure it is within the appropriate range.
  • T
    thomassethAug 27, 2025
    What to do if the compressor of my Bosch LV070 Heat Pump doesn't work but the fan runs and there is a freeze fault?
    • M
      Matthew PollardAug 27, 2025
      If your Bosch Heat Pump's compressor isn't running but the fan is, it could be due to a freeze fault in the water coil caused by no or low water flow. Check the water valves and/or pumps to ensure they are operating correctly. Also, check the water coil for any blockages.

Summary

Key Symbols and Safety Warnings

Key Symbols Explained

Explains warning symbols and keywords indicating risks and important information.

Critical Safety Warnings

Provides essential safety precautions for installation, servicing, and operation to prevent injury or damage.

Unit Installation and Preparation

Unit Controls and Startup Procedures

ECM Controls and Safety Features

Details on ECM interface, UPM board, and safety devices for unit operation.

Pre-Startup Checks and Operating Limits

System checkout, operating limits, and unit starting conditions before initial operation.

Troubleshooting Common Issues

Compressor and Fan Operation Faults

Diagnosing issues where the compressor or fan is not operating correctly, based on LED codes.

Dimensional and Wiring Diagrams

Electrical Wiring Diagrams

Schematics illustrating electrical connections, components, and UPM board layout.