MAP 5000 Appendices | en 77
Bosch Sicherheitssysteme GmbH Installation manual 2018.08 | 23 | F.01U.168.332
8.2.7 Alarm output via siren and communicator
Alarms, trouble events and other events must be output via siren and/or communicator.
4 For possible variants, refer to Sirens and communicator in accordance with EN50131 grade
3, page 62.
External alarm via siren
4 Activate the sirens at least for the following events (behavior items):
– External intrusion alarm
– External tamper alarm
4 Set the option Panel Wide Device.
Additional behavior items can be optionally added.
Remote alarm via communicator
4 Activate the communicator at least for the following events (Event Manager > Panel
Event Groups > Properties > Reportable Events):
– External intrusion alarm
– External tamper alarm
– Hold-up alarm
– Duress alarm
– Summary trouble
Additional reportable events can be optionally added.
8.2.8 Connection to a management system
Refer to IP Interface, page 56.
8.2.9 Printer connection
Connecting the DR2020T printer is permitted only for service purposes.
8.2.10 Access levels
The standard distinguishes between four access levels (AE):
– AE 1 Access for everyone, no authorization/code required
– AE 2 Access for users, user passcode required
– AE 3 Access for installers via control center or via RPS for MAP
– AE 4 Access for manufacturers via RPS for MAP
Selecting the access level
AE 1 Access for everyone, no authorization/code required
AE 2 Access for users, user passcode required
AE 3 Access for installers via control center
1. Open control panel enclosure.
The internal warning device is activated for 3 sec.
1
2. Switch to installer mode (refer to Installer button, page 66).
3. Enter installer passcode.
AE 3 Access for installers via RPS for MAP
1. Open control panel enclosure.
Internal warning device is activated for 3 sec.
1
or
authorize from RPS with an AE 2 user with corresponding permissions (control center:
main menu page 2 > RPS).
2. Establish a connection between the panel and RPS.