MAP 5000 Appendices | en 85
Bosch Sicherheitssysteme GmbH Installation manual 2018.08 | 23 | F.01U.168.332
Demand-driven connection with 25-hourly (AÜA-B25) or 5-hourly function monitoring
(AÜA-B5)
Existing connection with 3-minute (AÜA-S180) or 20-second function monitoring (AÜA-
S20)
Types Transmission procedure
EN 50131 SES
Class 1
AÜA-B25
Demand-driven connection with 25-hourly function
monitoring and voice annunciation
Class 2 Demand-driven connection with 25-hourly function
monitoring and simple digital transmission
Class 3 Demand-driven connection with 25-hourly function
monitoring and digital transmission
Class 4 AÜA-B5 Demand-driven connection with 5-hourly function monitoring
and digital transmission
Class 5 AÜA-S180 Existing connection with 180-second function monitoring and
digital transmission
Class 6 AÜA-S20 Existing connection with 20-second function monitoring and
digital transmission
Tab.8.7: Communicator types
8.4 Alarm reporting
ICP-MAP5000-COM and ICP-MAP5000-SC have an integrated alarm reporting functionality.
It can be used for alarm transmission systems according to EN50136-2 SP4 or DP3. For DP3
compliant transmission, the alternate transmission path has to be wireless.
In case of a fault on the primary connection to a receiver, ICP-MAP5000-COM and ICP-
MAP5000-SC are connecting to a backup receiver using the alternate transmission path.
The fault on the primary path is reported to the backup receiver and displayed on the control
center.
ICP-MAP5000-COM and ICP-MAP5000-SC can report to any alarm receiver supporting the
following protocols:
Conettix IP
SIA DC 09
VDS 2465
Transmission path faults are directly reported to the user via the MAP 5000 control center.
ICP-MAP5000-COM and ICP-MAP5000-SC have implemented layer 1 supervision for Ethernet
and wireless path.
ICP-MAP5000-COM and ICP-MAP5000-SC supervise the link to Ethernet and poll the wireless
network on checking for connection, signal strength and sign in status.
The communicator in ICP-MAP5000-COM and ICP-MAP5000-SC is realized as a pass-through
system.
The monitoring center, to which the panel is connected to, has to provide proof of availability
of the alarm transmission system.
For information security purposes, ICP-MAP5000-COM and ICP-MAP5000-SC provide the
possibility of encrypted transmission (AES 128, 192, 256).