46/128 Product information
Bosch Rexroth AG, CytroBox, RE 51057-B/11.19
Table 38: Error
S-0-0390 P-0-1300 S-0-0095 Cause Remedy
F2013 D300 D300: oil level of
tanktoo high
The monitoring of the oil level
indicates an alarm.
P-0-1291 > P-0-1389[74]
Check/reduce the oil volume in the tank.
Check the limit value.
Check the sensor output signal.
F2013 D301 D301: oil level of tank
too low
The monitoring of the oil level
indicates an alarm.
P-0-1291 < P-0-1389[73]
Check/increase the oil volume in the tank.
Check the limit value.
Check the sensor output signal.
F2013 D302 D302: particle
content S too high
The monitoring of the particle
concentration indicates an
alarm.
P-0-1424 > P-0-1389[65]
Check the limit value.
Check the sensor output signal.
Change the oil.
F2013 D303 D303: particle
content M too high
The monitoring of the particle
concentration indicates an
alarm.
P-0-1425 > P-0-1389[66]
Check the limit value.
Check the sensor output signal.
Change the oil.
F2013 D304 D304: particle
content L too high
The monitoring of the particle
concentration indicates an
alarm.
P-0-1426 > P-0-1389[67]
Check the limit value.
Check the sensor output signal.
Change the oil.
F2013 D305 D305: particle
content XL too high
The monitoring of the particle
concentration indicates an
alarm.
P-0-1427 > P-0-1389[68]
Check the limit value.
Check the sensor output signal.
Change the oil.
F2013 D306 D306: filter clogging
too high
The monitoring of the filter
contamination indicates an
alarm.
(P-0-1273 – S-0-0813)
> P-0-1389[31]
Check the limit value.
Check the sensor output signal.
Replace the filter element of the pressure filter.
F2013 D307 D307: oil
temperaturetoo high
The monitoring of the oil
temperature indicates an alarm.
P-0-1280 > P-0-1389[28]
Check the limit value.
Check the sensor output signal.
Reduce the load.
Check the oil cooling pump.
Check the water cooling unit.
F2013 D308 D308: oil
temperaturetoo low
The monitoring of the oil
temperature indicates an alarm.
P-0-1280 < P-0-1389[27]
Check the limit value.
Check the sensor output signal.
Heat the oil.
F2013 D309 D309: oxygen
contenttoo high
The monitoring of the air
inclusion indicates an alarm.
P-0-1270 > P-0-1389[8]
Check the limit value.
Check the sensor output signal.
Check the degassing function.
Reduce the required flow.
F2013 D310 D310: relative
humidity too high
The monitoring of the relative
humidity indicates an alarm.
P-0-1272 > P-0-1389[14]
Check the limit value.
Check the sensor output signal.
Check the drainage function.
Reduce the required flow.
F2013 D318 D318: leakage very
high
The monitoring of the leakage
flow indicates an alarm.
P-0-1293 > P-0-1389[40]
Check the limit value.
Check the sensor output signal.
Check the pump and replace it, if necessary.