Use the "IH_Temperature" function to read out the internal control tempera‐
ture in the "RIH_CMLx.library" library of the "IndraWorks" application program
(from version 11), see also documentation Rexroth IndraWorks 12VRS Basic
Libraries IndraLogic 2G, ( DOK-IL*2G*-BASLIB**V12-LI01-EN-P, parts num‐
ber R911333835).
Notice for control L45, L65 and
L85
Production failure possible due to control fail‐
ure resulting from overheating.
NOTICE
Operation is allowed up to 55 and if the air recirculates. If the air does not
recirculate, the fan has to be used.
If the internal temperature is 70 or higher, the display indicates the
"Temp !!!" warning.
If the internal temperature reaches approx. 80 ℃, the control switches off au‐
tomatically.
Use the "IH_Temperature" function to read out the internal control tempera‐
ture in the "RIH_CMLx.library" library of the "IndraWorks" application program
(from version 11), see also documentation Rexroth IndraWorks 12VRS Basic
Libraries IndraLogic 2G, ( DOK-IL*2G*-BASLIB**V12-LI01-EN-P, parts num‐
ber R911333835).
Notice for control L85
With the IndraControl L85 control, the fan is included in the scope
of delivery and is imperatively necessary for its operation. Infor‐
mation on the fan assembly is contained in chapter 10.4 "Mount‐
ing the Fan (if Necessary)" on page 34.