7 Technical Data
Processor Control L25: Renesas SH7785 with 576 MHz (CPU CLK)
Control L45: AMD LX800 with 500 MHz
Control L65: Intel Celeron M with 1.0 GHz
Control L85: Intel Core2Duo with 1.2 GHz
RAM Controls L45, L65 and L85:
Min. 256 MByte DRAM and min. 256 kByte RDS
1)
Optional:
8 or 16 MByte SRAM battery buffered
Control L25:
Min. 128 MByte DRAM and min. 256 kByte RDS
1)
Interfaces:
Interface to function
modules
Rexroth PC104
Plus
Interface to
I/O terminals
Rexroth Inline interface
Communication interfa‐
ces
(on L45, L65 and L85)
1 × Ethernet connection (RJ 45, 10Base-T,
100Base-TX)
Optional:
1 × third generation sercos master/slave interface
Optional:
1 × PROFIBUS DP master/slave interface
2 × Ethernet connection (RJ 45, 10Base-T, 100
Base-TX) for TCP/IP or RT Ethernet (PROFINET RT
or EtherNet/IP)
Communication interfa‐
ces
(on L25)
1 × Ethernet connection (RJ 45, 10/100 base-T)
1 × third generation sercos master/slave interface
Alternative option to the sercos master/slave inter‐
face
- 1 × PROFIBUS DP master/slave interface or
- 2 × Ethernet connection (RJ 45, 10Base-T, 100
Base-TX) for TCP/IP or RT Ethernet (PROFINET RT
or EtherNet/IP)
Ready Contact 1 × single-pin ready contact
Digital inputs and out‐
puts (only on L45, L65
and L85)
8 × electrically isolated digital inputs
8 × electrically isolated digital outputs
Weight 1.8 kg
1)
RDS - Remanent Data Storage
Remanent data is automatically written to the Compact Flash card after loss of
voltage and is restored after rebooting the control.
DOK-CONTRL-IC*LX5*****-IT01-EN-P
Rexroth IndraControl L25, L45, L65 and L85 Controls
Bosch Rexroth AG 17/65