Degree of protection IP 20
Dimensions See chapter 10.2 "Housing Dimensions" on page 26
Fig.7-1: Technical data
Voltage supply and current, power
consumption
The control is supplied with 24 V. The following values according to
DIN EN 61131-2 apply to the operating voltage:
Nominal voltage DC 24 V
Tolerance -15 %, +20 % (without residual ripple)
Residual ripple ±5 %
U
max
30 V
U
min
19.2 V
Power consumption of the controls from
U
LS
at nominal voltage and all connected
function modules and Inline terminals
Control L25: 2 A max.
Control L 45: 2.6 A max.
Control L65: 3.0 A max.
Control L85: 3.0 A max.
Current consumption of the controls from
U
M
and U
S
Max. 8 A in total
Power consumption (typically) of the con‐
trols (without connected I/O and function
modules)
Control L25: 8.7 W
Control L45: 14 W
Control L65: 18 W
Control L85: 21 W
Fig.7-2: Operating voltage and current, power consumption
Three operating voltages (segment voltage U
S
, the supply voltage U
LS
and
the main voltage U
M
) are to be applied to the control, see also chapter 10.7.4
"24 V Voltage Supply" on page 40.
Possible production failures due to malfunc‐
tions caused by feed backwards due to un‐
connected ground terminal.
NOTICE
Ensure that a ground terminal is always connected. In this way malfunctions
that are caused by feed backwards via I/O signals can be avoided.
Bosch Rexroth AG DOK-CONTRL-IC*LX5*****-IT01-EN-P
Rexroth IndraControl L25, L45, L65 and L85 Controls
18/65
Technical Data