6 Ambient Conditions
In operation Transport Storage
Max. surrounding
air temperature
+5 ℃ to +55 ℃ -25 ℃ to +70 ℃ -25 ℃ to +70 ℃
Relative humidity RH -2; 5 % to 95 %
according to DIN
EN 61131-2,
non-condensing.
RH -2; 5 % to 95 %
according to DIN
EN 61131-2,
non-condensing.
RH -2; 5 % to 95 %
according to DIN
EN 61131-2,
non-condensing.
Air pressure Up to 2,700 m
above MSL accord‐
ing to DIN 60204.
Above 2700 m
above MSL, see
chapter 10.7.8
"Notice for Use of
the Control above
2700 m above
MSL" on page 43.
Up to 3000 m
above MSL accord‐
ing to DIN 60204.
Above 2700 m
above MSL, see
chapter 10.7.8
"Notice for Use of
the Control above
2700 m above
MSL" on page 43.
Up to 3000 m
above MSL accord‐
ing to DIN 60204.
Above 2700 m
above MSL, see
chapter 10.7.8
"Notice for Use of
the Control above
2700 m above
MSL" on page 43.
Mechanical
strength
Max. vibration:
Frequency range:
10 Hz to 150 Hz
Excursion:
0.075 mm
at 10 Hz to 57 Hz
Acceleration: 1 g
at 57 Hz to 150 Hz
acc. to EN
60068-2-6
Max. shock:
15 g acc. to
EN 60 068-2-27, no
disturbance of the
function.
Max. shock:
15 g acc. to
EN 60 068-2-27, no
disturbance of the
function.
Fig.6-1: Ambient conditions
The surrounding air must be free from acids, alkaline solutions,
corrosive agents, salts, metal vapors, and other electrically con‐
ductive contaminants in high concentrations.
The ambient air must be dust-free. Housings and installation com‐
partments must at least comply with degree of protection IP 54
according to DIN VDE 0470-1.
Notice for control L25
Production failure possible due to control fail‐
ure resulting from overheating.
NOTICE
Operation is allowed up to 55 and if the air recirculates. If the air does not
recirculate, the fan has to be used.
If the internal temperature is 87 or higher, the display indicates the
"Temp !!!" warning.
If the internal temperature reaches approx. 92 ℃, the control switches off au‐
tomatically.