Power connector for the controls
UM
US
UL
FS
FN
UM
US
UL
FS
FN
PWR
UM
US
UL
FS
FN
PWR
1
2
3
Power connector for the control L45, L65 and L85 from the connector
set "R-IB IL CML S01-PLSET"
Power connector for the control L45, L65 and L85 from the connector
set "R-IB IL CML S04-PLSET"
Power connector for the control L25 from the connector set "R-IB IL
SCN-PWR IN-PWR"
Fig.10-23: Power connector for the control
Connector contact Signal (control L25) Signal (control L45, L65,
L85)
1.1 DC +24 V segment volt‐
age (U
S
)
DC +24 V segment volt‐
age (U
S
)
1.2 DC +24 V supply voltage
(U
LS
)
DC +24 V supply voltage
(U
LS
)
1.3 GND (U
LS
) (Ground supply
voltage)
GND (U
LS
) (Ground supply
voltage)
1.4 and 2.4 FE (functional earth
ground)
FE (functional earth
ground)
2.1 DC +24 V main voltage
(U
M
)
DC +24 V uninterruptable
power supply (UPS) is
currently not supported
2.2 DC +24 V main voltage
(U
M
)
DC +24 V main voltage
(U
M
)
2.3 GND (U
S
, U
M
) (Ground
main and segment volt‐
age)
GND (U
S
, U
M
) (Ground
main and segment volt‐
age)
Fig.10-24: Pin assignment of the power terminal of the control
For further information on the connection, please refer to the project planning
manual of the relevant control.
Possible malfunction if contacts 2.1 and 2.2
are interchanged
NOTICE
On controls L45, L65 and L85 with the device index smaller 201 (see also
chapter 2.1 "Product Identification" on page 7), contacts 2.1 and 2.2 are in‐
terchanged.
For further information on the connection, please refer to the project planning
manual of the controls.
DOK-CONTRL-IC*LX5*****-IT01-EN-P
Rexroth IndraControl L25, L45, L65 and L85 Controls
Bosch Rexroth AG 39/65
Mounting, Dismounting and Electrical Installation