R911299726 / 02 | Rexroth IndraControl VCP 05 Electric Drives and Controls | Bosch Rexroth AG 4-3
Technical Data
4.5 Interfaces
4.6 Central Processing Unit and Memory
Standard Interfaces
Variable Baud Rates and Data Formats
X3 SER1 TTY / 20 mA According to CL 2 and DIN 66 348 T1
Transmission Length: 0 - 1000 m (3280.84 ft.), Twisted
Pair, Shielded
Electrically Isolated
X3 SER1 RS485 According to DIN 66259-4
Transmission Length: 0 - 1200 m (3937.01 ft.), Twisted
Pair, Shielded
Electrically Isolated
X3 SER1 RS232c / X3 SER2 RS232c According to DIN 66259 T1, CCITT V.28
Transmission Length: 0 - 15 m (49.21 ft.), Layer-
stranded, Shielded
X3 SER1: Electrically Isolated
X3 SER2: Not Electrically Isolated
Field Bus Interfaces
Variable Baud Rates and Data Formats
X2.1 / X2.2 DeviceNet According to ISO 11898
Electrically Isolated
X2.1 / X2.2 INTERBUS Electrically Isolated
X2 PROFIBUS-DP Electrically Isolated
Central Unit
Central Unit Z84
Clock Frequency 10 MHz
Other Characteristics Watchdog Timer, Real-Time Clock, Temperature Com-
pensation of the Display, Battery Monitoring
Memory
Application Memory 256 KByte Flash
RAM 128 KByte Static CMOS-RAM, Battery-Backed