7-20 Bosch Rexroth AG | Electric Drives and Controls Rexroth IndraControl VCP 05 | R911299726 / 02
Interfaces
7.2.4 Pin Assignment
Fig. 7-29: 9-pin D-SUB female connector strip
Connector in the small operator terminal: 9-pin D-SUB female connec-
tor strip
7.2.5 Cable
Pin Designation Function
1 nc Not Connected
2 nc Not Connected
3 RxD/TxD-P Received Data / Transmitted Data Plus
4 CNTR-P Repeater Control Signal Plus
5 DGND Data Transmission Potential
6 VP Supply Voltage of Terminators Plus
7 nc Not Connected
8 RxD/TxD-N Received Data / Transmitted Data Minus
9 CNTR-N Repeater Control Signal Minus
Fig. 7-30: Pin assignment PROFIBUS DP
The D-SUB connector strips must be shielded sufficiently. See chapter
“Shielding D-SUB Connectors“ on page 7-22.
Any PROFIBUS DP-approved cables specified in the EN 50170 as ca-
ble type A can be used.
Impedance 136 to 165 Ohm
Capacity < 30 pf/m
Loop resistance 110 Ohm/km
Wire gauge 0.64 mm