Fig.5-18: Shield Connection XS1 (Control Lines)
Function
Connection point for the shields of lines connected to the control section and
of which the connectors do not have their own shield connection.
XS2, Shield Connection Motor Cable
Risk of damage to the drive controller by too
long screws!
Exclusively use screws of a maximum length of 12 mm for the thread of
shield connection XS2.
The connection consists of an M6 thread and is used for mounting the fixing
device for shield connection of the motor cable.
The accessory HAS02 contains all parts required for effective shield connec‐
tion of the motor cable (see index entry "Accessories").
5.3 Installation
5.3.1 General Information on How to Install the Drive Controller
Lethal electric shock by live parts with more
than 50 V!
Before working on live parts: De-energize installation and secure power
switch against unintentional or unauthorized re-energization.
Wait at least 30 minutes after switching off the supply voltages to allow dis‐
charging.
Check whether voltage has fallen below 50 V before touching live parts!