Installation 17/36
RE 30232-B/08.2020, Valve amplifier VT-MSPA, Bosch Rexroth AG
Table 7: Recommended cable variants
Table 8: Clamping range, rated connection
Min. Max.
Rigid 0.2 mm² 2.5 mm²
Flexible 0.2 mm² 2.5 mm²
Flexible with wire end ferrule 0.25 mm² 2.5 mm²
The length to be stripped is 10 mm each.
7.5.3 Connecting the individual contacts
Fig. 3: XG20/XG21: “PUSH-IN“ contact
Interface Maximum
length [m]
Cable type Minimum
cross-section
[mm
2
]
Remarks
Digital in/out 30 Unshielded 0.25 to 2.5 For 30 m or more, shielded cable required
50 Shielded 0.25 to 2.5
Command value 30 Twisted pair 0.25 to 2.5 For 30 m or more, shielded cable required
50 Twisted pair, shielded 0.25 to 2.5
Actual value 30 Twisted pair 0.25 to 2.5 For 30 m or more, shielded cable required
50 Twisted pair, shielded 0.25 to 2.5
Solenoid cable 20 Unshielded 1.0 to 1.5
50 Unshielded 1.5 to 2.5
Operating voltage 20 Unshielded 1.0 to 1.5
50 Unshielded 1.5 to 2.5
Solid wire
With wire end ferrule
Flexible wire
1.
2.
3.