24/46 Operation
BoschRexrothAG, RE51550-B/09.2019
Notice: The switching function can be designated in different ways:
Measurement
open
(0)
closed
(1)
open
(0)
closed
(1)
rising normally open contact
falling normally closed contact
NO (normally open)
hNO
rising normally closed contact
falling normally open contact
NC (normally closed)
hNC
5.1.7.2 Switching output x: Upper switching limit (switching point)
The upper switching limit for the switching output Outxis set in the following
submenu:
Switching point for OUT x
Setting range: [
O.lO
]...[
O.hI
]
Notice:
▶ The switching point must be selected within the range limits
(see menu Basic settings advanced functions).
▶ If the switching output OUTxhas been assigned the window
function, is displayed. The set value corresponds to the
upper window limit.
▶ If the switching output OUTxhas been assigned the frequency
output function, is displayed. The set value corresponds to
the frequency 100Hz.
5.1.7.3 Switching output x: Lower switching limit (switch-back point)
The lower switching limit for the switching output Outxis set in the following
submenu:
Switch-back point for OUT x
Setting range: [
O.lO
]...[
O.hI
]
Notice:
▶ The switch-back point must be selected within the range limits.
▶ If the switching output OUTxhas been assigned the window
function, is displayed. The set value corresponds to the
lower window limit.
▶ If the switching output OUTxhas been assigned the frequency
output function, is displayed. The set value corresponds to
the frequency 1Hz.