Operation 29/46
RE51550-B/09.2019, BoschRexrothAG
5.1.8.4 Analog output x: Determining the signal type
The analog output can be defined as a voltage or current output with different value
ranges. The setting is made in the menu:
The following options are available:
4mA to 20mA 2V to 10V 0V to 10V 0V to 5V
5.1.8.5 Analog output x: Testing the analog output
The analog output can be tested. The largest, medium and smallest analog values
can be output one after the other. The setting is made in the menu:
The following options are available:
Normal operation Output largest analog value
Output medium analog value Output smallest analog value
Important notice:
When the test is complete, set the function to normal operation
N.Op
.
5.1.9 Diagnosis options
The device is able to log the events for a switching output. Whenever the LED
is illuminated, this is considered an event. Thus the recording of the switching
processes depends on the setting of the switching function of the LED. The settings
and the evaluation can be made here.
▶ Press the q key to enter the main menu.
▶ Select the menu item
DIa
with the q and p keys.
From here you can access various diagnosis values and logs for
monitoring the measured values.
▶ Open the menu with the u key. Now you can change or call up the
diagnosis settings.
Important notice:
Only one switching output can be logged.
The switching output to be logged is selected in the menu item
Set Journal Out (
sj.OU
).