4.10.1.1 Upgrade Firmware
Path: (Menu)-More-Config-System Information-Maintain
Maintain: The Maintain button is located at left lower side in System Info. page. It is
the button to upgrade the firmware and Calibrate touch screen in paperless recorder
Upgrade Core System:
This is to upgrade firmware in paperless recorder. Contact factory/supplier for latest
firmware files. Please download firmware file first to USB stick, then, insert USB stick
at USB port at Paperless Recorder. Select ‘Update Core System” and then click on “OK”
button. It may take a few seconds to finish the process. Please note that power supply
should be not switched off during this upgrade process