31
Table 12 -- Menu Structure
*
(cont)
Menu Parameter
Parameter
Default
Value
Parameter
Range and Increment
[
EXPANDED P ARAMETER NAME
Notes
ADV AN CED
SETUP
(cont )
MATTCAL 0.0_F
(or C)
+ / --- 2 . 5 _F
( + / --- 1 . 4 _C)
SUPPL Y AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calib rati on supply air
tem p e ra t ure (SAT) sens or
OAS T CAL 1.0_F
(or C)
+ / --- 2 . 5 _F
( + / --- 1 . 4 _C)
OUTSIDE AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calib rati on outsi de air
tem p e ra t ure (O AT) sens o r
OAS H CAL 0% RH + / --- 1 0 % R H OUTSIDE AIR HUMIDITY CALIBRATION
Allows for the operator to adjust for an out of outsi de air enthalpy sensor
RA T CAL 0.0_F
(or C)
+ / --- 2 . 5 _F
( + / --- 1 . 4 _C)
RETURN AIR TEMPERATURE CALIBRA TION
Allows for the operator to adjust for an out of calibrat ion return air
temperature (RA) sensor
RA H CAL 0% RH + / --- 1 0 % R H RETURN AIR HUMIDITY CALIBRA TION
Allows for the operator to adjust for an out of calibrat i on ret urn air ent halpy
sensor
DA T CAL 0.0_F
(or C)
+ / --- 2 . 5 _F
( + / --- 1 . 4 _C)
DISCHARGEAIRTEMPERATURECALIBRATION
Allows for the operator to adjust for an out of calib rati on dis charg e air
tem p e ra t ure (DA T) sensor
2SP FAN DELAY 5 Minutes 0to20minutesin
1 minute increments
TIM E DELAY ON 2
nd
STAG E ECONO MIZ I NG
When in economizing mode this is the delay for the high speed fan to try to
sati s fy the call for second stage cooling before the first stag e mechanical
cooling is enabled.
CHECKOUT
[[[
DAMPER MINIMUM
POSITION
n/a n/a The checkout for the damper minimum posi ti ons is based on the system.
See Table 13.
DAMPER OPEN n/a n/a P os it ions damper to the full open positi on.
Exhaus t fan cont a c t s enab le during the DAM P ER OP EN test. Make sure
you pause in this mode to allow for exhaust contacts to energize due to the
delay in the system.
DAMPER CLOSE n/a n/a Pos it i ons damper to the fully closed positi on
CONNECT Y1---O n/a n/a C l oses th e Y1 --- O r el a y ( Y1 --- O) .
See CAUT IO N on page 38.
CONNECT Y2---O n/a n/a C l oses th e Y2 --- O r el a y ( Y2 --- O)
See CAUT IO N on page 38.
CONNECT AUX1---O n/a n/a E n e r g izes th e AU X 1 --- O o u tp u t. If AUX 1 --- O s e t t in g is:
S NONE --- not action taken
S ERV --- 24 Vac out. Turns on or signals an ERV that the conditions
are not good for economizing but are good for ERV operation.
[[
S S Y S --- 2 4 V a c o u t . I s s u e s a s y s t e m a l a r m .
CONNECT EXH1 n/a n/a Clos es the power exhaus t fan 1 relay (EXH1)