31
Table 12 -- Menu Structure
*
(cont)
Menu Parameter
Parameter
Default
Value
Parameter
Range and Increment
[
EXPANDED P ARAMETER NAME
Notes
ADV AN CED
SETUP
(cont )
MATTCAL 0.0_F
(or C)
+ / --- 2 . 5 _F
( + / --- 1 . 4 _C)
SUPPL Y AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calib rati on supply air
tem p e ra t ure (SAT) sens or
OAS T CAL 1.0_F
(or C)
+ / --- 2 . 5 _F
( + / --- 1 . 4 _C)
OUTSIDE AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calib rati on outsi de air
tem p e ra t ure (O AT) sens o r
OAS H CAL 0% RH + / --- 1 0 % R H OUTSIDE AIR HUMIDITY CALIBRATION
Allows for the operator to adjust for an out of outsi de air enthalpy sensor
RA T CAL 0.0_F
(or C)
+ / --- 2 . 5 _F
( + / --- 1 . 4 _C)
RETURN AIR TEMPERATURE CALIBRA TION
Allows for the operator to adjust for an out of calibrat ion return air
temperature (RA) sensor
RA H CAL 0% RH + / --- 1 0 % R H RETURN AIR HUMIDITY CALIBRA TION
Allows for the operator to adjust for an out of calibrat i on ret urn air ent halpy
sensor
DA T CAL 0.0_F
(or C)
+ / --- 2 . 5 _F
( + / --- 1 . 4 _C)
DISCHARGEAIRTEMPERATURECALIBRATION
Allows for the operator to adjust for an out of calib rati on dis charg e air
tem p e ra t ure (DA T) sensor
2SP FAN DELAY 5 Minutes 0to20minutesin
1 minute increments
TIM E DELAY ON 2
nd
STAG E ECONO MIZ I NG
When in economizing mode this is the delay for the high speed fan to try to
sati s fy the call for second stage cooling before the first stag e mechanical
cooling is enabled.
CHECKOUT
[[[
DAMPER MINIMUM
POSITION
n/a n/a The checkout for the damper minimum posi ti ons is based on the system.
See Table 13.
DAMPER OPEN n/a n/a P os it ions damper to the full open positi on.
Exhaus t fan cont a c t s enab le during the DAM P ER OP EN test. Make sure
you pause in this mode to allow for exhaust contacts to energize due to the
delay in the system.
DAMPER CLOSE n/a n/a Pos it i ons damper to the fully closed positi on
CONNECT Y1---O n/a n/a C l oses th e Y1 --- O r el a y ( Y1 --- O) .
See CAUT IO N on page 38.
CONNECT Y2---O n/a n/a C l oses th e Y2 --- O r el a y ( Y2 --- O)
See CAUT IO N on page 38.
CONNECT AUX1---O n/a n/a E n e r g izes th e AU X 1 --- O o u tp u t. If AUX 1 --- O s e t t in g is:
S NONE --- not action taken
S ERV --- 24 Vac out. Turns on or signals an ERV that the conditions
are not good for economizing but are good for ERV operation.
[[
S S Y S --- 2 4 V a c o u t . I s s u e s a s y s t e m a l a r m .
CONNECT EXH1 n/a n/a Clos es the power exhaus t fan 1 relay (EXH1)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bryant 549J 07A Series and is the answer not in the manual?

Bryant 549J 07A Series Specifications

General IconGeneral
BrandBryant
Model549J 07A Series
CategoryHeat Pump
LanguageEnglish

Related product manuals