83
Is there 24V at SEC-1 and SEC-2?
Is there 115V at L1 and L2?
Is there 115V going to switch?
Is circuit breaker closed?
Check for continuity in wire from circuit
breaker to furnace.
Close circuit breaker and go back to
START.
Is LED status light blinking rapidly without
a pause?
Check for correct line voltage polarity. If
units are twinned, check for proper low-
voltage (24V) transformer phasing.
Is LED status light blinking ON/OFF
slowly with a combination of short and
long flashes?
Determine status code. The status code
is a 2 digit number with the first digit
determined by the number of short
flashes and the second digit by the
number of long flashes?
To recall status code briefly remove and reconnect one RED wire from the draft
safeguard switch to display stored status code. You can also recall the previous
status code by momentarily shorting the TEST/TWIN terminal to Com24V terminal
until the LED goes out. LED will flash the status code of the previous fault or status
code #11 (1 short and 1 long flash) if there was no previous fault. After the control
repeats the code 4 times, the control will start the component test sequence. Once
initiated the control will turn the inducer ON at high-heat speed. The inducer will run
for the entire component test. The HSI, blower motor LO HEAT speed, HI HEAT
speed, and COOL speed will run for 10 – 15 seconds each. Gas valve and
humidifier will not be turned on. When the blower motor is turned OFF the inducer
will be switched to low-speed for 10 seconds.
Was there a previous status code other
than #11?
Go to section below for the status code
that was flashed.
Does the control respond to W/W1, W2,
Y1, Y/Y2, and G (24V) thermostat
signals?
Run system through a low-heat, high-
heat, or cooling cycle to check operation.
Status codes are erased after 72 hours.
Is 24V present at W/W1, W2, Y1, Y/Y2 or
G thermostat terminals on the furnace
control?
Check room thermostat or
interconnecting cable.
Disconnect all the thermostat wires from
the furnace control.
Does the problem repeat when using a
jumper wire?
The thermostat is not compatible with the
furnace control. Either install a ballast
resistor, connect the Com24V thermostat
terminal to the thermostat, or replace the
thermostat.
A11323A
Fig. 68 -- Troubleshooting Guide
925TA