INSTALLATION INSTRUCTIONS
R--410A Split System Heat Pump
CHS072 -- 121
NOTE: Read the entire instruction manual before starting
the installation
TABLE OF CONTENTS
SAFETY CONSIDERATIONS 2....................
INSTALLATION GUIDELINES 3..................
Rated Indoor Airfl ow (cfm) 3.....................
INSTALLATION 7 -- 14...........................
Jobsite Survey 7................................
Step 1 -- Plan for Unit Location 7..................
Step 2 -- Complete Pre--Installation Checks 8.........
Step3–PrepareUnitMounting Support 8...........
Step 4 -- Rig and Mount the Unit 8.................
Step 5 -- Complete Refrigerant Piping Connections 8...
Step 6 -- Install Accessories 12....................
Step 7 -- Complete Electrical Connections 12.........
Step 8 -- Wind Baffles for Low Ambient Control 14...
PRE-START-UP 16...............................
System Checks 16..............................
Turn On Crankcase Heaters 16....................
Preliminary Charge 16...........................
START--UP 16 -- 25..............................
CHS Units 16..................................
OPERATING SEQUENCE 26......................
Indoor (Supply) Fan 26..........................
Cooling Unit Without E conomizer 26...............
Cooling Unit With Economizer 27.................
Heating 27....................................
Defrost Cycle 27...............................
Supplemental Heating/Emergency Heating 28........
Cooling and Heating Shutdown 28.................
ROUTINE SYSTEM MAINTENANCE 28............
Quarterly Inspection
(and 30 days after initial start) 28..................
SERVICE 29 - 42................................
Refrigeration System 29.........................
Compressor Oil 29..............................
Servicing Systems on Roofs
with Synthetic Materials 29.......................
Liquid Line Filter Driers 29.......................
Filed Refrigerant Access Ports 29..................
Outdoor Coil Mete ring Devices 29.................
Refrigerant System Pressure Access Ports 30.........
Compressor Protection 30........................
Crankcase Heater 30............................
Commercial Defrost Board 30.....................
Comfort Alert Diagnostic Module 38...............
Lubrication 40.................................
Outdoor Coil Maint enance and
Clea ning Recommendations 40....................
Fastener Torque Values 42........................
TROUBLESHOOTING 43.........................
APPENDIX A
Air Conditioner and Heat Pump with R--410A
Quick Reference Guide 44........................
APPENDIX B
Wiring Diagram List 45..........................
APPENDIX C
Low
Ambient Option Factory Installed 46.........
START--UP CHECKLIST 51 -- 52...................

Questions and Answers

  • J
    jason83Aug 18, 2025
    Why does my Bryant CHS072 Heat Pump compressor operate continuously?
    • T
      Tyler LunaAug 18, 2025
      If your Bryant Heat Pump compressor runs continuously, it might be due to a dirty air filter, which you should replace. Alternatively, the unit may be undersized for the load, requiring you to decrease the load or increase the unit size. Check if the thermostat is set too low in cooling mode and reset it if needed. A low refrigerant charge could also be the cause, so locate and repair any leaks before recharging the system. Air in the system can also lead to continuous operation; in this case, recover the refrigerant, evacuate the system, and recharge it. Lastly, a dirty or restricted outdoor coil can cause this issue, so clean the coil or remove any restrictions.
  • M
    Michelle SinghAug 21, 2025
    How to fix excessive head pressure in Bryant CHS072?
    • C
      Christopher GrossAug 21, 2025
      Excessive head pressure in your Bryant Heat Pump can stem from several causes. Check for a dirty outside air or return air filter (if heating) and replace the filter. If cooling, a dirty outdoor coil could be the problem, so clean the coil. An overcharged refrigerant level can also cause this, requiring you to recover the excess refrigerant. Air in the system is another possibility; in this case, recover the refrigerant, evacuate the system, and recharge. Lastly, ensure that the condensing air is not restricted or short-cycling, and correct as necessary.
  • S
    Stacy ParkerAug 31, 2025
    What to do if Bryant CHS072 Heat Pump compressor won't start but outdoor fan runs?
    • B
      Brenda KaiserAug 31, 2025
      If your Bryant Heat Pump compressor won't start but the outdoor fan runs, it could be due to faulty wiring or loose connections in the compressor circuit; check the wiring and repair or replace as needed. The compressor motor might be burned out, seized, or have an internal overload open; determine the cause and replace the compressor or allow enough time for the internal overload to cool and reset. A defective run/start capacitor, overload, or start relay could also be the issue; determine the cause and replace the compressor. Finally, one leg of the 3-phase power might be dead; replace the fuse or reset the circuit breaker after determining the cause.
  • J
    Jennifer SmithSep 3, 2025
    Why is the head pressure too low in my Bryant CHS072 Heat Pump?
    • L
      Lindsay ChandlerSep 3, 2025
      Low head pressure in your Bryant Heat Pump can be caused by a low refrigerant charge, so check for leaks, repair them, and recharge the system. Defective compressor scroll plates can also lead to this issue, requiring you to replace the compressor. Additionally, a restriction in the liquid tube may be the cause, so remove the restriction.
  • M
    mark96Sep 7, 2025
    What causes excessive suction pressure in Bryant CHS072 Heat Pump?
    • A
      Amy EllisSep 7, 2025
      Excessive suction pressure in your Bryant Heat Pump can result from a high heat load; check for the source and eliminate it. Defective compressor scroll plates can also cause this, requiring you to replace the compressor. Another potential cause is an overcharged refrigerant level, in which case you should recover the excess refrigerant.
  • C
    Cody SalinasSep 12, 2025
    How to fix a noisy Bryant CHS072 compressor?
    • M
      Mary GoodwinSep 12, 2025
      If your Bryant Heat Pump compressor is making excessive noise, it might be rotating in the wrong direction. To resolve this, reverse the 3-phase power leads as described in the Start-Up section.
  • S
    stevensilvaNov 13, 2025
    Why won't my Bryant Heat Pump compressor and outdoor fan start?
    • C
      craigrossNov 13, 2025
      If the compressor and outdoor fan of your Bryant Heat Pump won't start, it could be due to several reasons. First, there might be a power failure, in which case you should call your power company. It could also be a blown fuse or tripped circuit breaker, so replace the fuse or reset the breaker, identifying the cause. Other potential causes include a defective thermostat, contactor, transformer, control relay, or capacitor, which would need replacement. Insufficient line voltage or incorrect wiring can also be culprits, requiring correction or rewiring. The thermostat setting might be too high, so lower it below room temperature. Finally, tripped high or low pressure switches or freeze-up protection could be the issue; refer to the sections on ‘Excessive head pressure’ and ‘Suction pressur...
  • T
    Tina ZavalaNov 23, 2025
    What to do if suction pressure is too low in Bryant CHS072?
    • J
      johnblakeNov 23, 2025
      Low suction pressure in your Bryant Heat Pump can be attributed to several factors. A dirty air filter (if in cooling mode) can cause this, so replace the filter. If heating, a dirty or heavily iced outdoor coil might be the issue; clean the outdoor coil and check the defrost cycle operation. A low refrigerant charge is another potential cause, so check for leaks, repair them, and recharge the system. A restricted metering device or low side can also lead to low suction pressure, so remove the source of the restriction. Insufficient indoor airflow (in cooling mode) can be a factor; increase the air quantity and replace the filter if necessary. If the temperature in the conditioned area is too low, reset the thermostat. A restricted field-installed filter drier should be replaced. If the ou...
  • W
    williamadamsNov 27, 2025
    Why does my Bryant Heat Pump compressor cycle on and off frequently?
    • J
      Jacqueline SmithNov 27, 2025
      If your Bryant Heat Pump compressor cycles more than it should, it could be due to several reasons. The system may have a refrigerant overcharge or undercharge, requiring you to recover the refrigerant, evacuate the system, and recharge it to the nameplate value. A defective compressor could also be the cause, so replace it after determining the reason for failure. Other potential issues include insufficient line voltage, a blocked outdoor coil, a dirty air filter, or a defective run/start capacitor, overload, or start relay; determine the cause and correct or replace the component. A defective thermostat can also cause cycling, so replace the thermostat. Lastly, a faulty outdoor-fan (cooling) or indoor-fan (heating) motor or capacitor, or a restriction in the refrigerant system could be t...

Bryant CHS072 Specifications

General IconGeneral
ModelCHS072
TypeHeat Pump
RefrigerantR-410A
Compressor TypeScroll
Energy Star CertifiedYes
Phase1
Voltage208/230V