24 S5 Battery Validation System
10
Re-establish
communications.
a. From the System Configuration window, click
Clear Memory, then select Relearn Connections.
b. When prompted to clear the alarms, click Yes.
c. In the Communications window, look at the
alarm LEDs. They should be off. If one of them
is not off, either the BVM system is not installed
correctly, or there is a problem with one of the
batteries.
11
If needed, continue
to diagnose errors.
From the Module Configurations
window, click Module Diagnostics.
Action How to do it Picture