Operating Manual 25
Starting Up
12
Select the module to
view.
In the Controller Module Diagnostics
window, click on the module that has
the alarm in the BVM file.
In this example, module 12 will be
used.
13 Note the error.
a. Look for leads with an
unusual voltage reading. For
example:
0.00 voltage: May
indicate a disconnected
lead or missing VSL
fuse.
0.01 voltage: Could be
normal, if voltage is
being read over a battery
interconnect (battery bar
or strap)
Unusually high or
double voltage: May
indicate switched leads.
Negative voltage:
Usually indicates
switched leads.
b. Click Close when done.
Action How to do it Picture