52 S5 Battery Validation System
2
Go to the Controller
Settings window.
a. In the Communications window, click
Advanced>> to display the lower buttons.
b. Click the Controller Settings button.
3
Decide how what
time and how often
measurements will
be taken
automatically.
a. From the Controller Settings window, click on
the Controller Measurement Setup tab.
b. In the Next Measurement section, click on the
Date field to set the date of the next
measurement.
c. Highlight each section of the Time field (hour,
minute, second, AM/PM) and click the up and
down arrows to choose the time of day that
measurements will be taken.
d. In the Measurement Interval field, click the up
and down arrows to select how often
measurements will be taken, in Days. If you want
measurements to be taken more than once a day,
make the Day field be zero (0).This will cause
the Hour field to be selectable.
e. Click OK when done.
4
Determine the range
that will be shown in
graphed
measurement
displays.
a. Click on the System Limits tab in the
Controller Settings window.
b. The maximum and minimum voltage levels
were chosen for your system to best show
activity in a meaningful way. But if you want to
show more detail, you can make the range
smaller by increasing the Min.Voltage field and/
or decreasing the Max. Voltage field.
c. The Ambient fields are set to reflect an
average room temperature of 72 degrees
Farenheit (22 degrees Celcius). If the average
battery environment is hotter or cooler than this,
raise or lower the Max. Ambient and Min.
Ambient settings accordingly.
d. Click OK when done.