34 S5 Battery Validation System
3. Insert VSL Wires into the VM-24’s Plugs, then Plug In
d. Keep the VSL wires together and as close to the
batteries as possible.
e. Cut the wires near the VM-24 and strip them
a. See the order VSL wires go into plugs (see Appendix)
b. Use WAGO connector ‘hook’ open pin hole & insert wire c. Insert all the wires as directed
4. Drawing of person reading a
paper
VM-24 Module 1 Wire color: Yellow
VSL No. Jar #
+/
Neg
VM-24 Module 1
Terminal #
Length,
feet
VSL group 1
VSL group 7
11+ 1 40
22+ 2 40
33+ 3 40
43
Ne
440
VSL group 1
VSL group 7
VSL group 2
VSL group 8
54+ 5 40
65+ 6 40
76+ 7 40
86
Ne
840
VSL g
roup 9
VSL group 2
VSL group 8
97+ 9 40
10 8 + 10 40
VSL g
roup 9
NOTE: The Battery Wiring List
shown at right is an
example only. For your
installation, see the wire
list in the Appendix of this
book.