0911 - 21
english
6 FACTORY SETTING
PA
1
Description Range Default PE
2
SET1 Set-value 1 LS1 + US1 0 Pr1
SET2 Set-value 2 LS2 + US2 1 Pr1
HY1 Switch hysterisis 1
dependent on measurement
range
-1 Pr1
Switch hysterisis 2
dependent on measurement
range
-1 Pr1
Ft Controller type onF = ON/OFF; Pid = PID Pid Pr2
LS1 Lowest set-value 1
Lower measurement range +
SET1
min Pr2
Lowest set-value 2
Lower measurement range +
SET2
min Pr2
US1 Largest set-value 1
Upper measurement range +
SET1
max Pr2
Largest set-value 2
Upper measurement range +
SET2
max Pr2
S1C Control effect Output 1 in = inverse; dir = direct in Pr2
Control effect Output 2 in = inverse; dir = direct in Pr2
ouc
Ac 0...250 sec 0 Pr2
on
Minimum switch-on time
for a relay
0...250 sec 0 Pr2
Minimum waiting time
between two consecutive
activations of the same
load
0...120 min 0 Pr2
Alarm limits are absolute
values or related to the
set-value
rE = relative; Ab = absolute rE Pr2
Lower Alarm Limit
(ALC = rE; ALC = Ab)
dependent on measurement
range
10 Pr2
Upper Alarm Limit
(ALC = rE; ALC = Ab)
dependent on measurement
range
10 Pr2
Switch hysterisis for
temperature alarms
dependent on measurement
range
2Pr2
ALd
Alarm delay time during
the operation
0...999 min 15 Pr2
dAO 0...23.5 h 1.3 Pr2
1
Parameter
2
Programming level