7
4.6 Electrical data
Connections:
DIN EN 175301-803 Design A
for cable plug Type 2509 or Type 2518
Operating
voltage:
Type 6013:
24 V DC ±10%, max. residual ripple 10%
24 V/50 Hz, 230 V/50 Hz
Type 6013A:
24 V DC ±10%, max. residual ripple 10%
230 V/50 Hz
Voltage tolerance: ±10%
Nominal power:
WWA: 8 W (5 W, 10 W)
WWB: AC 7 W (9 W), DC 8 W
Impulse version DC: 7 W
Nominal oper-
ating mode:
Continuous operation, duty cycle 100%
for block installation:
5 W continuous operation a. A.
8 W intermittent operation 60% (30 min)
5 INSTALLATION
5.1 Safety instructions
DANGER
High pressure danger.
▶ Switch o the pressure before working on the device or system.
Vent or empty the lines.
Danger from electrical voltage.
▶ Before working on the device or system, switch o the power
supply. Secure it against reactivation.
▶ Observe the applicable accident prevention and safety regula-
tions for electrical devices.
WARNING!
Risk of injury due to improper installation.
▶ Installation work may be carried out by authorised technicians
only, with the appropriate tools.
Risk of injury due to unintentional activation of the system and
uncontrolled restart.
▶ Secure the system against unintentional activation.
▶ Following installation, ensure a controlled restart.
English