EasyManua.ls Logo

Burnham FREEDOM - Method 1: Primary;Secondary Piping

Burnham FREEDOM
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
45
Method 1: Primary/Secondary Piping
Thismethodcanbeusedinheat-onlyapplicationsasshowninFigure9.2orwithanindirectwaterheaterasshown
inFigure9.3.Thismethodreliesonprimary/secondarypumpingtoensurethattherequiredowisalwaysmaintained
throughtheboiler.Inthissystem,theowratethroughtheboileriscompletelyindependentoftheowratethroughthe
heatingsystem.UsethefollowingguidelinestoensurethattheboilerwillhavetherequiredowshowninTable9.1
regardlessoftheowintheheatingsystem.
1) PrimaryLoopPiping-Sizetheprimarycirculatorandpipingtoobtainthedesignowratethroughtheheatingsystem
asyouwouldonanyotherheatingsystem.Allpipingbetweentheexpansiontankandsecondaryconnectionteesmust
beatleastaslargeasthatshowninTable9.5,column(a).Inordertokeeptheowratesintheprimaryandsecondary
loopsindependentofeachother,provideatleast8diametersofstraightpipeupstreamoftherstsecondaryteeand4
diametersdownstreamofthesecondsecondarytee.Keepthedistancebetweentheexpansiontankandtherstsecondary
teeasshortaspractical.
2) SecondaryLoop(“BoilerLoop”)Piping–AllpipingmustbethesizeshownfortheboilerinTable9.5,column(a).To
sizethecirculator:
a) SelectoneoftheboilerwaterowratesshowninTable9.5,column(b)fortheboilerbeinginstalled.When
selectingtherequiredboilerowrate,keepinmindthatiftheowrateintheprimaryloopexceedstheow
ratethroughtheboiler,itwillnotbepossibletoobtaina180°Fsupplytemperatureintheprimaryloop.Thisis
becausethesupplywaterexitingtheboilerwillbemixedwithcoolersystemreturnwaterbeforeenteringthe
radiation.
b)Countallttingsintheplannedsecondaryloop(thesecondaryloopconsistsoftheshadedpipinginFigure
9.4a).Indoingso,donotcountthesecondaryconnectiontees,unions,orthettingssuppliedwiththeboiler
(thesehavealreadybeenaccountedfor).
c) UsingTable9.7,ndtheequivalentlengthsofallttingsinthesecondaryloop.Totaltheseequivalentlengths
andaddthemtothetotallengthofplannedstraightpipeinthesecondaryloop.Theresultisthetotalequivalent
lengthofthesecondaryloop.
d) UsingTable9.5,ndtheboilersizebeinginstalledandselectaboilersecondarycirculatorthatshowsa
“maximumequivalentlength”(columne)inexcessofthetotalequivalentlengthcalculatedinStep2c.
3)
IndirectWaterHeaterLoopPiping(IfIndirectWaterHeaterisUsed)–AllpipingmustbethesizeshowninTable9.6,
column(a).Iftheindirectwaterheaterconnectionsaresmallerthanthepipesizecalledforincolumn(a),reducethe
pipesizeattheindirectwaterheaterconnections.Tosizethecirculator:
a) CountallttingsintheplannedIndirectWaterHeaterLoop(theindirectwaterheaterloopconsistsofthe
shadedpipinginFigure9.4b).Indoingso,youwillbecountingsomepipingandttingswhicharecommonto
theheatingsystemsecondary(“boilerloop”)pipingandwhichwerecountedinStep2aabove.Donotcountthe
elbowsorttingssuppliedwiththeboiler.
b) UsingTable9.7,ndtheequivalentlengthsofallttingsintheindirectwaterheaterloop.Totaltheseequivalent
lengthsandaddthemtothetotallengthofplannedstraightpipeintheindirectwaterheaterloop.
Theresultisthetotalequivalentlengthoftheindirectwaterheaterloop.
c) UsingTable9.6,ndtheboilersizebeinginstalledandselectanindirectwaterheaterloopcirculatorthatshows
a“maximumequivalentlength”(columnf)inexcessofthetotalequivalentlengthcalculatedinStep3b.
Example – Assume that a FCM120 is to be installed in a heating system along with an Alliance indirect water heater.
A total of 15 ft of straight pipe will be installed between the boiler and the primary loop. A total of 20 ft of straight
pipe will be installed between the boiler and the indirect water heater. Fittings are arranged as shown in Figure
9.3. A 9.0 GPM ow is required in the boiler loop. The MS-40 requires a ow rate of 8 GPM and has a head loss
of 3.0 ft.
Total ttings in Secondary loop (“boiler loop”):
6 90 Elbows
2 Runs of Tees
1 Swing Check
2 Isolation Valves
Note: Unions, Secondary Connection Tees, and factory supplied ttings are ignored.
Calculate total equivalent length from Table 9.7:
15ft Straight Pipe + 6 Elbows x 2.75 + 2 Runs of Tees x 1.75 + 1 Swing Check x 7 + 2 valves x 0.6 = 43.2
equivalent feet straight pipe. From Table 9.5, we see that a Taco 0014 will pump 9 GPM through a FCM120 with 61
equivalent feet of pipe, so the Taco 0014 is OK.

Other manuals for Burnham FREEDOM

Related product manuals