41
8) InstallationofVerticalExhaustTerminal-UsetheterminalsuppliedbytheventsystemmanufacturershowninTable
7.5.Attachtotheventsystem,followingtheassemblyinstructionsinthismanualforthestainlessventsystembeing
used.
9) AssemblyoftheAirIntakeSystemandAirIntakeTerminals:
a)AssembletheairintakesystemusingeithergalvanizedorPVCpipe.
b) IfPVCpipingisused,usePVCcementtoassemblethePVCintakesystemcomponents.
c)Ifgalvanizedpipingisused,useatleasttwosheetmetalscrewsperjoint.Sealtheoutsideofalljoints.
d)3”galvanizedsmokepipewilltinsidetheinletcollarontheboiler.DependingupontheexactODofthepipeused,
itmaybenecessarytocrimpthispipe.Securewithasingle#10sheetmetalscrewthroughtheholeintheinletcollar
andsealtheoutsideofthejointwithsilicone.IfPVCisusedfortheintakesystem,useashortpieceof3”galvanized
pipetoconnectthePVCtotheboiler.SiliconetheoutsideofthejointbetweenthePVCandgalvanizedpipe.
e)Horizontalintaketerminalisa90degreeelbowpointingdown.Elbowshouldprotrudethesamedistancefromthe
wallastheexhaustterminal.
f) Verticalairintaketerminalconsistsofa180degreebend(composedoftwo90degreeelbows)asshowninFigure
7.10.
g)Installarodentscreen(notsupplied)intheinletterminal.Useascreenhaving1/2”(2x2)orlargermesh.
F. Condensate Trap and Drain Line
Allcondensatewhichformsintheboilerorventsystemcollectsinthesumpundertheheatexchangerandleavesthe
boilerthroughthecondensatetrap.Thistrapallowscondensatetodrainfromthesumpwhileretaininguegasesintheboiler.
ThetrapissuppliedlooseandmustbeinstalledasshowninFigure7.51.Alengthofdrainhoseissuppliedwiththeboiler
andisconnectedtothetrapasshowninFigure7.51.Notethefollowingwhendisposingofthecondensate:
a)Ifthecondensatedrainlinemustbeextended,constructtheextensionfromPVCorCPVCpipe.Insertthehose
providedwiththeboilerintotheendoftheextensionasshowninFigure7.51.
b) Condensateisslightlyacidic.Donotusemetallicpipeorttingsinthecondensatedrainline.Donotroutethedrain
linethroughareasthatcouldbedamagedbyleakingcondensate.
c)Somejurisdictionsmayrequirethatthecondensatebeneutralizedbeforebeingdisposedof.Disposeofcondensatein
accordancewithlocalcodes.
d)Donotroute,orterminate,thecondensatedrainlineinareassubjectedtofreezingtemperatures.
e)Ifthepointofcondensatedisposalisabovethetrap,itwillbenecessarytouseacondensatepumptomovethe
condensatetothedrain.Insuchcases,selectacondensatepumpthatisapprovedforusewithcondensingfurnaces.If
overowfromthispumpwouldresultinpropertydamage,selectapumpwithanoverowswitchandusethisswitch
toshutdowntheboiler.Alternatively,ifheatisanecessity,usetheoverowswitchtotriggeranalarm.
f) DonotattempttomovethetrapfromthelocationshowninFigure7.51.Donotattempttosubstituteanothertrapfor
theoneprovidedwiththeboiler.
g)TheventshowninFigure7.51mustbeleftopenforthetraptoworkproperly.
WARNING
FAILURE TO INSTALL THE CONDENSATE TRAP AND CONDENSATE DRAIN IN ACCORDANCE
WITH THE ABOVE INSTRUCTIONS COULD CAUSE FLUE GAS TO ENTER THE BUILDING,
RESULTING IN PERSONAL INJURY OR DEATH.
CAUTION
BOILER CONDENSATE IS CORROSIVE. ROUTE CONDENSATE DRAIN LINE IN A MANNER SUCH
THAT ANY CONDENSATE LEAKAGE WILL NOT CAUSE PROPERTY DAMAGE.
SOME JURISDICTIONS MAY REQUIRE THAT CONDENSATE BE NEUTRALIZED PRIOR TO
DISPOSAL.