EasyManua.ls Logo

Burnham FREEDOM - Page 40

Burnham FREEDOM
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
40
6) AssemblyofProtechFasNSeal
a) FasNSealGeneralNotes:
• Donotcut4”FasNSealpipe.ConsultFasNSealinstructionsformethodofcuttingother3”pipe.
• OrientFasNSealventcomponentssothatthearrowsonthepipinglabelsareinthedirectionofuegasow.
• Supporthorizontalpipingsectionsatintervalsof6feetorless.
• VerticalventingsystemsmustbesupportedbyatleastoneFasNSealsupport.Anadditionalverticalsupportis
requiredafteranyoffset.
b)RemovethehoseclampshippedontheFCMventcollar.Bendthethreehoseclamptabsonthiscollaroutward
slightly.Cleantheexteriorofthemaleendoftherstpieceofpipeandtheinsideoftheventcollarontheboiler.
Removedirt,grease,andmoisturefromthesurfacestobesealed.Onthemaleendofthepipe,applya¼”widebead
ofhightemperaturesiliconeapproximately¼"fromthemaleendofthepipe.Insertthemaleendofthepipeintothe
boilerventcollaruntilitbottomsout.Applyanadditionalbeadofsiliconeovertheoutsideofthejointandtheseams
ontheventcollarandsmoothout(Figure7.50).Replaceandtightentheclampontheventcollar.
c)AllotherjointsintheFasNSealventingsystemrelyonagasketinthefemaleendofthepipeforaproperseal.
d)Alignthelongitudinalseamofbothpipes.Insertthemaleendofthesecondpipeintothefemaleendoftherstpipe
untilthebeadonthemaleendcontactstheareonthefemaleend.
e)Tightenthelockingbandwithanutdriver.
f) Repeat(d)and(e)fortheremainingFasNSealcomponents.
g)Allowthesiliconetocureperthesiliconemanufacturersinstructionsbeforeoperatingtheboiler.
7) InstallationofHorizontalExhaustTerminal:
a)Whenstainlesssteelventingisused,useU.S.BoilerstainlessexhaustterminalP/N8110701.Theouteredgeofthis
terminalmustbebetween6and12inchesfromthesurfaceofthewall.The joint between the terminal and the last
piece of pipe must be outside of the building.
b)Maleendofterminalwilltintothefemaleendofanyoftheapprovedstainlessventsystems.
c)Applyaheavybeadofsiliconetothemaleendoftheterminalbeforeinsertingitintothelastpieceofpipe.Orientthe
terminalsothattheseamintheterminalisat12:00.
d)Smooththesiliconeovertheseambetweentheterminalandthelastpieceofpipe,applyingadditionalsiliconeif
necessarytoensureatightseal.
e)Allowthesiliconetocureperthesiliconemanufacturer’sinstructionsbeforeoperatingtheboiler.
FIGURE 7.50: FASNSEAL CONNECTION TO VENT COLLAR

Other manuals for Burnham FREEDOM

Related product manuals