DuraVent PolyPro - ULC S636 listed Polypropylene special gas vent system.
•SelkirkPolyue-ULCS636listedPolypropylenespecialgasventsystem.
Centrotherm InnoFlue SW - ULC S636 listed Polypropylene special gas vent system.
DuraVent FasNSeal Flex - UL 1738 listed Stainless Steel special gas vent system.
Use PVC and/or CPVC for the air intake system. PVC may be used for all air intake piping between the intake terminal
and the boiler.
When CPVC and/or PVC pipe is used, it must be joined using primer and cement that is listed for use with the pipe
material being joined (PVC, CPVC, or CPVC to PVC).
2. Vent Kit Available for Use with this Boiler - The following vent kit is available for CPVC/PVC vent systems installed with
this boiler in the USA:
107039-02 - 3” CPVC/PVC Vent Kit
These kit include the following:
(1) 30” CPVC Straight Pipe
(1) 90 degree short bend CPVC Elbow
(1) Straight PVC Coupling (for exhaust terminal)
(1) 90 degree PVC Elbow (for intake termination)
(2) Rodent screens
The CPVC Pipe and elbow supplied with these kits are not listed to ULC S636 and may not be used in Canada.
3. Maximum Vent and Air Intake Lengths - The maximum length of the vent air intake piping depends upon the vent option
selected and the boiler size. See Tables 7.5, 7.13 or 7.21 for the maximum vent lengths. These maximum lengths apply
to both the vent and intake piping (e.g. Option 1 may have up to 135ft of intake and 135ft of vent piping). For all vent
systems,thelengthsshowninTables7.5,7.13and7.21areinadditiontotherst90°elbow.Ifmoreelbowsaredesired,
the maximum allowable vent length must be reduced by the amount shown in Table 7.1 for each additional elbow used.
Terminationttingsarenevercounted.
ItisrecommendedthatalleldsuppliedPVCorCPVCelbowsbe“1/4Bend”(Sanitary90°Elbow)or“LongSweep1/4
Bend” type elbows (Figure 7.2). In this manual “sanitary” and “long sweep” elbows are treated as having the same equivalent
length.
Example:
A 3” twin pipe horizontal CPVC/PVC vent system is planned for a horizontally vented 135 MBH model which has the
following components in the vent system:
1 ft CPVC Straight Pipe
90 CPVC Elbow (short bend)
1-1/2 ft CPVC Straight Pipe
Coupling
10 ft PVC Straight Pipe
90 PVC Elbow (Sanitary Elbow Design)
15 ft PVC Straight Pipe
PVC Coupling Terminal
The Vent Option #1 column in Table 7.5 describes a horizontal direct vent system using 3” CPVC and PVC pipe. From this
column, we see that the boiler may have a vent length of up to 135ft. The rst CPVC 90 degree elbow is not considered. From
Table 7.1, we see that the equivalent length of the 90 PVC elbow is 4ft and that the equivalent length of the coupling is 0ft.
The total equivalent length of the planned venting system is therefore:
1ft (Straight CPVC) + 0ft (rst short bend CPVC 90 Elbow) + 1.5ft (Straight CPVC) + 0ft (Coupling) + 10ft (Straight PVC)
+ 4ft (PVC 90 Sanitary Elbow) + 15ft (Straight PVC) + 0ft (Coupling Terminal) = 31.5ft.
Since Table 7.1 shows a maximum allowable vent length of 135ft, the planned vent system length is acceptable
TheexventingusedonsomeoftheVerticalTwinPipeandSplitVentOptionsalsoreducesthemaximumallowablevent
length. See Sections VII-C or VII-D for details.