EasyManua.ls Logo

Burnham K2WTC - Page 19

Burnham K2WTC
160 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
19
107774-01- 9/17
NOTICE
Do not exceed maximum vent/combustion air system length. Refer to Tables 7.1B, 7.5, 7.13, and 7.21
in this section for maximum vent/combustion air system length.
Use only vent and combustion air terminals and terminal locations shown in Tables 7.5, 7.13 and
7.21.
5. Minimum Vent and Air Intake Lengths - Observe the minimum vent lengths shown in Tables 7.5, 7.13 and 7.21.
6. Clearances to Combustibles - Maintain the following clearances from the vent system to combustible construction:
Vent - 1/4” (also observe clearances through both combustible and non-combustible walls - see 9)
Air Intake - 0”
Concentric Portion of Concentric Terminals - 0”
7. Pitch of Horizontal Vent Piping - Pitch all horizontal vent piping so that any condensate which forms in the piping will run
towards the boiler.
Pitch CPVC/PVC vent piping 1/4” per foot.
Pitch Polypropylene vent piping 5/8” per foot.
VII. Venting A. Vent System Design (continued)
Table 7.1B: Vent/ Air Intake Fitting Equivalent Length
CPVC/PVC Fitting
Equivalent
Length (ft)
PolyPro, Polyue
or InnoFlue
Vent Fitting
Equivalent
Length (ft)
FasNSeal Vent Fitting
Equivalent
Length (ft)
3” 90° Elbow (“Sanitary Bend”) 4.0 3” 90° Elbow 8.7
3” 90° Elbow 4.0
3” 45° Elbow 2.0 3” 45° Elbow 4.6
3” 45° Elbow 2.0
3” 90° Elbow (“Short Bend”) 10.0
3” Straight Tee 18.0
3” Coupling 0.0
3” Boot Tee 8.0
Figure 7.2: CPVC and PVC Elbows

Related product manuals