VII. Venting D. Design Requirements Unique to Split Vent Systems (continued)
Table 7.21: Summary of Split Vent System Options (cont.)
Option # 17 18
Illustrated in Figure 7.23, 7.24 7.23, 7.24
Pipe Penetration
Through Structure
Vent Roof Roof
Intake Wall Wall
Material
Vent
Centrotherm
Innoue
(Ridgid/Flex)
DuraVent
FasNSeal
(Stainless,
Ridgid/Flex)
Intake PVC PVC
Nominal Diameter
Vent 3” 3”
Intake 3” 3”
Min Equivalent Vent Length:
Models
135 48” 48”
150 52” 52”
180 52” 52”
Max Equivalent Vent Length (Note 1):
Models
135 135ft 135ft
150 135ft 135ft
180 135ft 135ft
Rigid Vent Terminals
Vent
Not Permitted
Intake
Flex Termination
& Components
(Masonry Chimney
Chase)
Vent IFCK03**
2SVSCKIT03**
2SVFLXCN03**
Intake
90 Elbow
w/Screen
90 Elbow
w/Screen
Flex Termination &
Components (B-Vent
Chimney Chase)
Vent IFBK03**** 2SVFLXR03
Intake
90 Elbow
w/Screen
90 Elbow
w/Screen
** Specify length in feet.
**** Specify Flex length and B vent diameter (e.g. IFBK032506 includes 25ft of ex and used with 6” B vent).
Note 1: Max vent lengths shown also apply to the intake. Flex vent reduces the maximum allowable vent length in
some applications. See equivalent lengths for ex vent shown in Table 7.14 and sizing example on page 32.
All vertical terminals require compatible roof ashing and storm collars.