EasyManua.ls Logo

Burnham K2WTC - Page 72

Burnham K2WTC
160 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
72
107774-01 - 9/17
Figure 9.0: Factory Supplied Piping and Trim Installation
IX. System Piping (continued)
9. Drain Valve (required) – Install the drain valve (provided by the installer) as shown in Figure 9.2.
10. Low Water Cut-off (may be required by local jurisdiction) – Protection of this boiler against low water and/or
inadequateowisprovidedbytheUL353certiedowswitchbuiltintotheboiler.Thisisawatertubeboilerand
thisowswitchisthereforetheonlyeffectivewaytoprovidesuchprotection.SectionHG614(c)ofthe2015
ASMEboilerandPressureVesselCoderecognizestheuseofalistedowswitchinlieuofalowwatercut-offon
water tube boilers.
In the event that a local jurisdiction insists upon the installation of a low water cut-off with this boiler, refer to Part
XI and the low-water cut-off manufacturer’s instructions for proper wiring. Install the low water cut-off in the supply
piping at the point prescribed the local jurisdiction (generally at a point above the boiler).
If a probe type low water cut-off is used, be certain that it is located at a point in the piping from which air can
escape to an automatic air vent. Generally, this means that there should be no down-turns in the piping between
the low water cut-off and the point where the automatic air vent is installed. Failure to do this may result in nuisance
boiler shut-downs due to small amounts of air trapped around the probe.

Related product manuals