EP203 AUTOMATIC EXTINGUISHER PANEL
Approved Document No. DFU0002032 Rev 4 • EP203 AUTOMATIC EXTINGUISHER PANEL INSTALLATION MANUAL • Page 17 of 45
Ign iting Actua tor (Me tron ) W i ri n g
The extinguishant output is capable of supplying up to 3 amps for the maximum
duration (50 milliseconds) to an igniting actuator.
The total series resistance of the actuator(s) and wiring should NOT exceed 7 ohms.
Figure 9 : Typical Igniting Actuator Circuit Wiring
Wi r ing fo r one actuator :
Wi r ing fo r m u l ti ple ac tuators :