Dis ablem ents
The Disablements menu allows the temporary disabling, or enabling of the
extinguishant system, detection zones, sounders, monitored inputs, relays and RSUs. The
Disablements menu is available at both Access Levels 2 and 3. Any active disablements
are displayed at the EP203 panel by the General Disablement and relevant disablement
yellow LEDs lit steady.
Note: It is recommended all disablements are immediately enabled when no longer
required as they can have a major effect on how the system works.
Di sable Ext ing
This sub-menu allows the disabling/enabling of the extinguishant system.
1. From the Disablements menu, select the Disable Exting sub-menu.
2. Press the Accept button to disable/enable the extinguishant system.
3. Press the Escape button to return to the Disablements menu.
Note: ‘Exting System Disabled’ will also be displayed at any RSUs connected on the
system.
Di sable Zone
This sub-menu allows the disabling/enabling of one, or more of the panel’s three
detection zones. Disabled zones do not report fire, or fault conditions.
1. From the Disablements menu, select the Disable Zone sub-menu.
2. Select the detection zone(s) to be disabled/enabled using the Scroll (up) and Scroll
(down) buttons.
3. Press the Accept button to disable/enable a selected zone.
4. Press the Escape button to return to the Disablements menu.
Di sable Sounder
This sub-menu allows the disabling/enabling of the fire sounders from sounding in a fire
condition.
1. From the Disablements menu, select Disable Sounder.
2. Press the Accept button to disable/enable the sounder circuit.
3. Press the Escape button to return to the Disablements menu.
Di sable SndrDel
The sounder delay sub-menu allows the disabling/enabling of a fire sounder delay in a
fire condition.
1. From the Disablements menu, select Disable SndrDel.
2. Press the Accept button to disable/enable the delay on the sounder circuit.
3. Press the Escape button to return to the Disablements menu.