EP203 AUTOMATIC EXTINGUISHER PANEL
Approved Document No. DFU0002032 Rev 4 • EP203 AUTOMATIC EXTINGUISHER PANEL INSTALLATION MANUAL • Page 31 of 45
Resound F i re
This sub-menu enables/disables a resound of the alarm sounders.
1. From the Commissioning menu, select Resound Fire.
2. Select either the enabled, or disabled option using the Scroll (up) and Scroll (down)
buttons.
3. Press the Accept button to confirm the changes. The Commissioning menu is displayed.
Clean Star t
This sub-menu clears the panel’s memory back to its factory default settings.
1. From the Commissioning menu, select Clean Start. The panel requests the
confirmation code.
2. Press the Scroll (up), Accept, Scroll (down) and Escape buttons.
3. Press the Accept button to confirm the clean start. The Commissioning menu is
displayed.