EP203 AUTOMATIC EXTINGUISHER PANEL
Approved Document No. DFU0002032 Rev 4 • EP203 AUTOMATIC EXTINGUISHER PANEL INSTALLATION MANUAL • Page 5 of 45
In addition to the basic requirements of EN12094-1, the EP203 panel meets the
following criteria:
EN12094-1 Section 4.17 ‘Delay of extinguishing signal (option with
requirements)’ delay time from 0 to 60 seconds.
EN12094-1 Section 4.18 Signal representing the flow of extinguishing agent
(option with requirements)to indicate the flow of the extinguishing agent.
EN12094-1 Section 4.19 ‘Monitoring of the status of components (option with
requirements)’ by way of a low pressure switch input.
EN12094-1 Section 4.20. Emergency hold device (option with requirements)to
enable the extinguishant delay time to be extended.
EN12094-1 Section 4.21 Control of flooding time (option with requirements)’ to
deactivate the releasing output after a set time period.
EN12094-1 Section 4.23 ‘Manual only mode (option with requirements)to
disable the release of extinguishant via automatic detection devices.
EN12094-1 Section 4.26 Triggering of equipment outside the system (option
with requirements)’ by way of first and second stage contacts, etc.
EN12094-1 Section 4.27 Emergency abort device (option with requirements)to
inhibit the extinguishing signal until the emergency abort device has been
deactivated.
EN12094-1 Section 4.30 ‘Activation of alarm devices with different signals
(option with requirements)to indicate pre-discharge and released warnings
using different sounds.
In addition to the basic requirements of EN54-2, the EP203 panel meets the following
criteria:
EN54-2 Section 7.8 ‘Fire alarm devices (option with requirements)’ to enable an
audible warning to be sounded throughout the premises upon the detection of a
fire condition or the operation of a manual call point.
EN54-2 Section 7.11. ‘Delay of the actioning (option with requirements)of fire
alarm devices (sounders) so that an alarm may be verified before a premises is
evacuated.
EN54-2 Section 7.13. ‘Alarm counter (option with requirements)’ to record the
number of instances the panel enters the fire alarm condition.
EN54-2 Section 10Test condition (option with requirements)’ to allow the
automatic resetting of zones in alarm for testing purposes.
In addition to the requirements of EN54-2, the EP203 panel has volt-free relay contacts
for fire and local fire that operate upon a fire condition. These are to be used for local
control and signaling.
www.acornfiresecurity.com
www.acornfiresecurity.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the C-TEC EP203 and is the answer not in the manual?

C-TEC EP203 Specifications

General IconGeneral
BrandC-TEC
ModelEP203
CategoryFire Alarms
LanguageEnglish

Related product manuals