LEVEL A
Function Options
[Factory settings] shown in brackets
Linear Input Scaling
Please read in conjunction with Linear Input Set-up Procedure on page 6.
An.hi -1999 to 9999 [1000]
Adjusts required scale maximum
An.Lo -1999 to 9999 [0]
Adjusts required scale minimum
hi.in 0.1 to 50.0 [50.0]
Configure input maximum
Lo.in 0.0 to 49.9 [10.0]
Configure Input minimum
This setting must be at least 0.1 less than the setting for
hi.in
above.
Note: Refer to Linear Input conversion factors detailed in the Set-up Procedure on page 6.
dECP 000.0 to 00.00 [0000]
Scale resolution
NB. Once the Linear Input option has been selected, the setting here over-rides the scale
resolution setting
di.SP
in Level 2 and will affect the following display readings:
Level A:
An.hi
;
An.Lo
;
Set.3
;
hYS.3
Level 1:
bAnd
;
ofSt
;
SPrr
;
SEt2
;
bnd.2
Level 2:
hiSC
;
LoSC
Level 3:
SPAn
;
ZEro
;
rEAd
;
tECh
SP3 SETTINGS
SP3.A [nonE] dV.hi dV.lo bAnd FS.hi FS.Lo EoP
Main SP3 operating mode
SP3.b [nonE] LtCh hoLd Lt.ho
Subsidiary SP3 operating mode
SEt.3 0 to 2500 [0]
SP3 setpoint adjustment
hyS.3 0.1 to 100% of hiSC [20]
Set SP3 hysteresis
10
LEVL A
Function Options
[Factory settings] shown in brackets
brn.3 [uPSC] uPSC or dnSC
Sensor burn-out / break protection
Select upscale or downscale
rEV.3 [3d] 3d or 3r
Reverse SP3 output mode
Select direct or reverse operation
Will be affected by dECP settings in Level A