USER CHECK LIST 90/140BM
LAMP ACTION
UNIT DOES NOT OPERATE
MAINS RED
OFF
FAULT AMBER
OFF
FRIDGE FAULT
1 AND/OR 2
AMBER
1/2
OFF Check mains supply, -external fuses - isolator etc.
DEFROST WHITE
OFF
WATERFLOW GREEN OFF
MAINS RED
ON Water flow inadequate
FAULT AMBER
OFF Check water pump to restore flow rough machine. Check waterflow rate, check
internal control MCB
FRIDGE FAULT
1 AND/OR 2
AMBER
1/2
OFF
DEFROST WHITE
OFF Check ermostat set point. Check internal control M.C.B.
WATERFLOW GREEN
OFF
MAINS RED
ON
FAULT AMBER
OFF
FRIDGE FAULT
1 AND/OR 2
AMBER
1/2
OFF 12 hour timer timing out or standby switch set to 0
DEFROST WHITE
OFF
WATERFLOW GREEN ON
MAINS RED
ON Check air flows are not restricted.
FAULT AMBER
OFF
FRIDGE FAULT
1 AND/OR 2
AMBER
1/2
ON Check HP/LP cut out switch and reset (red buttons). NOTE LP Switch is Auto reset on
Y machines. Fridge CCT 1 cut out switches in LH side of machine - electric box facing.
Fridge CCT 2 cut out switches mounted below console. Check compressor motor circuit
breakers. Check Compressor ermal overloads.
DEFROST WHITE OFF
WATERFLOW GREEN ON
MAINS RED
ON
FAULT AMBER
ON
FRIDGE FAULT
1 AND/OR 2
AMBER
1/2
OFF
Check fan motor circuit breakers. Check so start (if fitted).
DEFROST WHITE
OFF Check linked in external equipment is not e cause of e fault.
WATERFLOW GREEN
OFF
MAINS RED
ON
FAULT AMBER
ON
FRIDGE FAULT
1 AND/OR 2
AMBER
1/2
OFF Check water flow is not inadequate and water pump etc to restore flow to machine.
DEFROST WHITE
OFF
WATERFLOW GREEN OFF
Continued Overleaf