Installation Manual June 2018 • Rev. 1.6
Specifications
See power supply notes in Appendix section for more information.
Controller Power Requirements (No Readers Attached, Ethernet Connected)
Maximum Current (all Relays, LEDs ON)………………………………… 350 mA
Temperature Range
Operating ……………………………………………………………………………….. -20˚C to 60˚C
Relative Humidity
Operating ………………………………………………………..……………………… 20% to 80%
Auto Resettable Fuses
MAP1 Main 12V DC……………………………………………………………………………1 A
Each Reader Pair ……………………………………………………………………………………1 A
Output Relays
All Relays (8 per panel) Form ‘C’ …………………………………SPDT 6 A @ 30 VDC
Inputs per Provisioned Doors (Supervised or Non-Supervised)
Door Contact (2 per MAP1) …………………………Requires normally closed contact
(On/Off door switch)
Exit Button (2 per MAP1) ………………..………………Requires normally open contact
(Momentary push button switch)
Reader Cable
Wiegand Readers ........................................ 6 conductor (twisted pair not required)
.............................................................................. 22 AWG, overall shield
........................................................................ 152 m [500 ft] max. Length
NOTE: Consult reader specifications as 18-gauge wire may be required for power
Dimensions & Weight
MAP1 Enclosure ……………………………………………..4.6” (W) x 4.9” (H) x 2.0” (D)
[11.7 cm (W) x 12.4 cm (H) x 5.1 cm D)]
Enclosure plus Controller Weight ..................................................... 500 g [17.6 oz]