“EVD Evolution TWIN” +0300006EN - rel. 2.6 - 31.01.2019
13
2.12 General connection diagram
G
G0
G
G0
VBAT
COMA
NOA
1
3
24
NET
Tx/RxGND
DI1
S4
S3
S2
S1
GND
DI2
VREF
2 AT
24 Vac
230 Vac
35 VA
shield
shield
shield
shield
with batterywithout battery
G
G0
VBAT
COMx
NOx
1
3
2
4
Sporlan
SEI / SEH
/ SER
DANFOSS
ETS / CCMT
EVD4
PC
EVD4 service USB adapter
EEV driver
4
Tx/Rx
GND
pCO
GNDGND
RS485
Modbus®
pCO
1
20
21
4
EVDCNV00E0
CVSTDUM0R0
pCO
Analog - Digital Input Network
OPEN A
CLOSE A
OPEN B
CLOSE B
A
B
COMB
NOB
1
3
24
G
G0
VBAT
EVD
G
G0
VBAT
35 VA
ULTRACAP
24 Vac
230 Vac
2 AT
EVD evolution
TWIN
shield
TRADRFE240
TRADRFE240
4
1
2
3
CAREL E
X
V
VALVE B
CAREL E
X
V
VALVE A
89
10
11
12
13
23
S
A
17
18 19
14
S
B
15
16
7
6
1
20
4
21
22
3
4
21
ALCO
EX5/6
EX7/8
5
1
4
C
D
E
F
B
Tx/Rx
GND
DI1
S4
S3
S2
S1
GND
DI2
VREF
1
21
20
4
4
21
3
A
EVD0000T0*: tLAN version
EVD0000T3*: tLAN version
EVD0000T1*: pLAN version
EVD0000T4*: pLAN version
EVD0000T2*: RS485 version
EVD0000T5*: RS485 version
1
2
Tx/Rx
GND
DI1
S4
S3
S2
S1
GND
DI2
VREF
Tx/Rx
GND
DI1
S4
S3
S2
S1
GND
DI2
VREF
Tx/Rx
GND
DI1
S4
S3
S2
S1
GND
DI2
VREF
Tx/Rx
GND GND
DI1
S4
S3
S2
S1
GND
DI2
VREF
1
20
Tx/Rx
DI1
S4
S3
S2
S1
GND
DI2
VREF
L
2
Fig. 2.o
Key:
1 green 21 black
2 yellow 22 blue
3 brown 23 computer for conguration/supervision
4 white A Connection to EVD0000UC0
5 computer for conguration B Connection to ratiometric pressure transducer (SPKT00**R0)
6 USB/tLAN converter C Connection to electronic pressure probe (SPK**0000) or piezoresistive
pressure transducer (SPKT00*C00)
7 adapter
8 ratiometric pressure transducer driver A D Connection as positioner (4 to 20 mA input)
9 NTC probe driver A E Connection as positioner (0 to 10 Vdc input)
10 ratiometric pressure transducer driver B F Connection to combined pressure/temperature probe (SPKP00**T0)
11 NTC probe driver B L Connection to Float level sensor (cod. LSR00*3000)
12 digital input 1 congured to enable driver A control
1
The maximum length of the connection cable to the EVD0000UC0 module
is 5 m.
13 digital input 2 congured to enable driver B control
14 voltage-free contact (up to 230 Vac) driver B
2
The connection cable to the valve motor must be 4-wire shielded, AWG 22
Lmax= 10 m or AWG14 Lmax= 50 m.
15 solenoid valve driver B
16 alarm signal driver B
17 voltage-free contact (up to 230 Vac) driver A
18 solenoid valve driver A
19 alarm signal driver A
20 red