EasyManua.ls Logo

Carel EVD Evolution Twin - 11. TECHNICAL SPECIFICATIONS

Carel EVD Evolution Twin
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ENG
“EVD Evolution TWIN” +0300006EN - rel. 2.6 - 31.01.2019
57
11. TECHNICAL SPECIFICATIONS
Power supply
(Lmax= 5 m)
24 Vac (+10/-15%) to be protected by external 2 A type T fuse.
24 Vdc (+10/-15%) 50/60 Hz to be protected by external 2 A type T fuse. Use a dedicated class 2 transformer (max 100 VA).
Power input 16.2 W ; 35 VA
Emergency power supply 22 Vdc+/-5%. (If the optional EVBAT00400 module is installed), Lmax=5 m
Insulation between relay output and
other outputs
reinforced; 6 mm in air, 8 mm on surface; 3750 V insulation
Motor connection 4-wire shielded cable AWG 22, Lmax 10 m or AWG 14, Lmax= 50 m
Digital input connection Digital input to be activated from voltage-free contact or transistor to GND. Closing current 5 mA; Lmax< 30 m
Probes (Lmax=10 m;
with shielded cable
less than 30 m)
S1 ratiometric pressure probe (0 to 5 V):
• resolution 0.1 % fs; • measurement error: 2% fs maximum; 1% typical
electronic pressure probe (4 to 20 mA):
• resolution 0.5 % fs; • measurement error: 8% fs maximum; 7% typical
remote electronic pressure probe (4 to 20mA). Maximum number of drivers connected=5
combined ratiometric pressure probe (0 to 5 V):
• resolution 0.1 % fs; • measurement error: 2 % fs maximum; 1 % typical
4 to 20 mA input (max 24 mA):
• resolution 0.5% fs; • measurement error: 8% fs maximum; 7% typical
0 to 5 V input:
• resolution 0.1 % FS; • measurement error: 2% FS maximum; 1% typical
S2 low temperature NTC:
• 10 k at 25°C, -50T90 °C; • measurement error: 1°C in range -50T50 °C; 3°C in range +50T90 °C
high temperature NTC:
• 50 k at 25°C, -40T150 °C; • measurement error: 1.5 °C in range -20T115 °C, 4 °C in range outside of -20T115 °C
Combined NTC:
• 10 k at 25 °C, -40T120 °C; • measurement error: 1 °C in range -40T50 °C; 3°C in range +50T90 °C
0 to 10 V input (max 12 V):
• resolution 0.1 % fs; • measurement error: 9% fs maximum; 8% typical
S3 ratiometric pressure probe (0 to 5 V):
• resolution 0.1 % fs; • measurement error: 2% fs maximum; 1% typical
electronic pressure probe (4 to 20 mA):
• resolution 0.5 % fs; • measurement error: 8% fs maximum; 7% typical
remote electronic pressure probe (4 to 20mA). Maximum number of drivers connected=5
4 to 20 mA input (max 24 mA):
• resolution 0.5% fs; • measurement error: 8% fs maximum; 7% typical
combined ratiometric pressure probe (0 to 5 V):
• resolution 0.1 % fs, • measurement error: 2 % fs maximum; 1 % typical
0 to 5 V input:
• resolution 0.1 % FS; • measurement error: 2% FS maximum; 1% typical
S4 low temperature NTC:
• 10 k at 25°C, -50T105°C; • measurement error: 1°C in range -50T50 °C; 3°C in range 50T90°C
high temperature NTC:
• 50 k at 25°C, -40T150°C; • measurement error: 1.5°C in range -20T115°C 4°C in range outside of -20T115°C
Combined NTC:
• 10 k at 25°C, -40T120°C; • measurement error 1°C in range -40T50°C; 3°C in range +50T90°C
Relay output normally open contact; 5 A, 250 Vac resistive load; 2 A, 250 Vac inductive load (PF=0.4); Lmax=50 m;
UL: 250 Vac, 5 A resistive, 1A FLA, 6A LRA, pilot duty D300. 30000 cycles
VDE: 1(1)A PF=0.6
Power supply to active probes (V
REF
) +5 Vdc ±2% o 12 Vdc ±10% depending on type of probe set
RS485 serial connection Lmax=1000 m, shielded cable
tLAN connection Lmax=30 m, shielded cable
pLAN connection Lmax=500 m, shielded cable
Assembly DIN rail
Connectors plug-in, cable size 0.5 to 2.5 mm
2
(12 to 20 AWG)
Dimensions LxHxW= 70x110x60
Operating conditions -25T60°C (don’t use EVDIS* under -20°C); <90% RH non-condensing
Storage conditions -35T60°C (don’t store EVDIS* under -30°C), humidity 90% RH non-condensing
Index of protector IP20
Environmental pollution 2 ( normal )
Resistance to heat and re Category D
Immunity against voltage surges Category 1
Rated impulse voltage
2500V
Type of relay action 1C microswitching
Insulation class 2
Software class and structure A
Conformity Electrical safety: EN 60730-1, EN 61010-1, UL873, VDE 0631-1
Electromagnetic compatibility: EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4; EN61000-3-2, EN55014-1,
EN55014-2, EN61000-3-3.
Tab. 11.a

Table of Contents