8. TABLE OF PARAMETERS
8.1 Table of parameters, driver A
user *
Parameter/description Def. Min. Max. UOM
Type **
CAREL SVP
Modbus®
Note
CONFIGURATION
A Network address pLAN: 30
others: 198
1 207 - I 11 138 CO
A Refrigerant:
0= user dened;
1= R22 2= R134a 3= R404A 4= R407C 5= R410A
6= R507A 7= R290 8= R600 9= R600a 10= R717
11= R744 12= R728 13= R1270 14= R417A 15= R422D
16= R413A 17= R422A 18= R423A 19= R407A 20= R427A
21= R245FA 22= R407F
23=R32 24=HTR01 25= HTR02
26=R23 27 = R1234yf 28 = R1234ze 29 = R455A 30 = R170
31 = R442A 32 = R447A 33 = R448A 34 = R449A 35 = R450A
36 = R452A 37 = R508B 38 = R452B 39 = R513A 40 = R454B
41 = R458A
R404A - - - I 13 140 -
A Valve:
0= user dened 13= Sporlan SEH 175
1= CAREL E
X
V 14= Danfoss ETS 12.5-25B
2= Alco EX4 15= Danfoss ETS 50B
3= Alco EX5 16= Danfoss ETS 100B
4= Alco EX6 17= Danfoss ETS 250
5= Alco EX7 18= Danfoss ETS 400
6= Alco EX8 330Hz recommend
CAREL
19= Two E
X
V CAREL connected
together
7= Alco EX8 500Hz specic Alco 20= Sporlan SER(I)G,J,K
8= Sporlan SEI 0.5-11 21= Danfoss CCM 10-20-30
9= Sporlan SER 1.5-20 22= Danfoss CCM 40
10= Sporlan SEI 30
23= Danfoss CCM T 2-4-8
11= Sporlan SEI 50
24= Disabled
12= Sporlan SEH 100
CAREL E
X
V - - - I 14 141
A Probe S1:
0= user dened
Ratiometric (OUT=0 to 5 V) Electronic (OUT=4 - 20 mA)
1= -1 to 4.2 barg 8= -0.5 to 7 barg
2= 0.4 to 9.3 barg 9= 0 to 10 barg
3= -1 to 9.3 barg 10= 0 to 18.2 bar
4= 0 to 17.3 barg 11= 0 to 25 barg
5= 0.85 to 34.2 barg 12= 0 to 30 barg
6= 0 to 34.5 barg 13= 0 to 44.8 barg
7= 0 to 45 barg 14= remote, -0.5 to 7 barg
15= remote, 0 to 10 barg
16= remote, 0 to 18.2 barg
17= remote, 0 to 25 barg
18= remote, 0 to 30 barg
19= remote, 0 to 44.8 barg
20= 4 to 20mA external signal
21= -1 to 12.8 barg
22= 0 to 20.7 barg
23= 1.86 to 43.0 barg
24= CAREL liquid level
25 = 0...60,0 barg
26 = 0...90,0 barg
27 = external signal 0…5 V
Ratiometric:
-1 to 9.3 barg
---I16143CO