“EVD Evolution TWIN” +0300006EN - rel. 2.6 - 31.01.2019
41
user *
Parameter/description Def. Min. Max. UOM
Type **
CAREL SVP
Modbus®
Note
C CUSTOMIZED REFRIGERANT
Dew a high -288 -32768 32767 - I 107 234
Dew a low -15818 -32768 32767 - I 108 235
Dew b high -14829 -32768 32767 - I 109 236
Dew b low 16804 -32768 32767 - I 110 237
Dew c high -11664 -32768 32767 - I 111 238
Dew c low 16416 -32768 32767 - I 112 239
Dew d high -23322 -32768 32767 - I 113 240
Dew d low -16959 -32768 32767 - I 114 241
Dew e high -16378 -32768 32767 - I 115 242
Dew e low 15910 -32768 32767 - I 116 243
Dew f high -2927 -32768 32767 - I 117 244
Dew f low -17239 -32768 32767 - I 118 245
Bubble a high -433 -32768 32767 - I 119 246
Bubble a low -15815 -32768 32767 - I 120 247
Bubble b high -15615 -32768 32767 - I 121 248
Bubble b low 16805 -32768 32767 - I 122 249
Bubble c high 30803 -32768 32767 - I 123 250
Bubble c low 16416 -32768 32767 - I 124 251
Bubble d high -21587 -32768 32767 - I 125 252
Bubble d low -16995 -32768 32767 - I 126 253
Bubble e high -24698 -32768 32767 - I 127 254
Bubble e low 15900 -32768 32767 - I 128 255
Bubble f high 10057 -32768 32767 - I 129 256
Bubble f low -17253 -32768 32767 - I 130 257
C Faulty closure alarm status
0/1=no/yes
001-D4948
C Battery charge delay 0 0 250 min I 135 262 CO
ALARM CONFIGURATION
C Low superheat alarm delay (LowSH)
(0= alarm disabled)
300 0 18000 s I 43 170 -
C Low evaporation temperature alarm delay (LOP)
(0= alarm disabled)
300 0 18000 s I 41 168 -
C High evaporation temperature alarm delay (MOP)
(0= alarm disabled)
600 0 18000 s I 42 169 -
C High condensing temperature alarm delay (HiTcond)
SELECT WITH PROG. CONT.
600 0 18000 s I 44 171 CO
C Low suction temperature alarm threshold -50 -85 (-121) 200 (392) °C (°F) A 26 25 -
C Low suction temperature alarm delay
(0= alarm disabled)
300 0 18000 s I 9 136 -
VALVE
C EEV minimum steps 50 0 9999 step I 30 157 -
C EEV maximum steps 480 0 9999 step I 31 158 -
C EEV closing steps 500 0 9999 step I 36 163 -
C EEV rated speed 50 1 2000 step/s I 32 159 -
C EEV rated current 450 0 800 mA I 33 160 -
C EEV holding current 100 0 250 mA I 35 162 -
C EEV duty cycle 30 1 100 % I 34 161 -
C Synchronise position in opening 1 0 1 - D 20 19 -
C Synchronise position in closing 1 0 1 - D 21 20 -
Tab. 8.a
* User level: A= Service (installer), C= manufacturer.
** Type of variable: A= Analogue; D= Digital; I= Integer
CO= parameter settable from driver A or from driver B