FCM electronic regulator - Preliminary version Cod. +302235300 - Rel. 2.0 del 30/11/98
30
PARAMETERS CONCERNING KEYPAD/REMOTE CONTROL
C50
Enabling Keypad and Remote control:
0=keypad disabled; rem.control: param. P and St1 can be modified, par. C can't be seen.
1=keypad enabled; rem. control: param. P and St can be modified, param. C can't be seen.
2= keypad disabled; rem.control disabled (param. P and St can only be displayed).
3=keypad enabled; rem. control disabled (param. P and St can only be dispalyed).
4=keypad enabled; rem.control enabled.
0 4 4 -
C51
Code to enable the remote control 0 99 0 -
PARAMETERS CONCERNING SERIAL CONNECTION
C52
Type of serial connection:
0=no connection
1=supervisory network (protocol Supervisor 3.0)
2=connection to pLAN network
0 2 1 -
C53
Serial address 0 255 0 -
C54
Baud-rate (if C52=1); 0=1200 Bd, 1=2400 Bd, 2=4800 Bd, 3÷32=9600 Bd
Data destination address
0
0
3
32
0
0
-
C55
Frame (if C52=1)
0= (8,N,2) 1= (8,N,1) 2= (8,E,2) 3= (8,E,1) 4= (8,O,2)
5= (8,O,1) 6=(7,N,2) 7=(7,N,1) 8= (7,E,2) 9= (7,E,1)
10= (7,O,2) 11 (and beyond )= (7,O,1)
Page (if C52=2)
0
0
11
255
0 -
C56
Delayed response 0 255 50 ms
C57
Enabling hardware board 0 255 255 %
Default = factory-set value;
(*) parameters not accessible in SLAVE mode
(**) for FCM0002000 default is 30.0
(***) for FCM0002000 default is 0.0