7.12.3 Counter reset
To reset the counter (parameter d4):
heaterSteam
Alarm
Steam
Drain
Fill
x1000
SEL
reset
PRG
drain
heaterSteam
Alarm
Steam
Drain
Fill
x1000
SEL
reset
PRG
drain
1. Press PRG until the display shows P0;
2. Press UP or DOWN until reaching parameter d4;
3. Press the SEL button to display the value of the counter preceded for
1 second by the unit of measure;
4. Press simultaneously UP or DOWN for 5 s until the value is reset,
preceded by the display of the unit of measure.
7.12.4 Total drainage (manual)
Procedure:
heaterSteam
Alarm
Steam
Drain
Fill
x1000
SEL
reset
PRG
drain
1. Within the  rst 5 s after the appliance is turned on, press and hold
simultaneously the buttons UP and DOWN;
2. Total drainage is launched (view dr”).
To complete drainage early:
1. Press UP and DOWN for 5 s.